background image

 

Innova S.r.l.

 

Pag.  26 

N420229A_ManualHRW_rev2.en.docx

 

 

 

 

6

 

COMMISSIONING AND METHOD FOR USE 

6.1.1

 

WORKING VERSION  -I- 

 

The unit is completely manually 
controlled way by the user, through the 
touch command to CNV wall; 

there is the possibility of connecting the 
sensors humidity regulator and air 
quality; 

 

 

 

switch 3V 

 

Below are given the keys present 
on the main form: 

Meaning of the main display keys: 

 

Allows the ignition / 
keyboard unit is turned 
off 

 

Button for changing the set 
temperature   

 

Keys for selecting the 
ventilation speed:   

Silent / Nominal / 
maximum 

 

Key for summer / winter 

 

 

Key to the operation 
nominal speed and 
sensor 

 

ALARM signal 

Viewing the main mask keys 

 

6.1.1.1

 

TURNING ON THE UNIT POWER OFF   

-The unit can be enabled and disabled through the On / Off button on the display. 

 

   

 

Power On / Off Unit 

 

 

 

 

Summary of Contents for HRW DOMO

Page 1: ...50 000 CF P IVA 01827470228 Iscrizione REA nr 180610 Num reg Imprese TN 10656 Numero Meccanografico TN025148 www innovaenergie com Pag 1 N420229A_ManualHRW_rev2 en docx INSTALLATION USE AND MAINTENANC...

Page 2: ...N COMPONENTS OF THE UNITY 9 1 1 10 PACKING AND TRANSPORT 9 1 1 11 RECEPTION CONTROL AND HANDLING 10 1 1 12 REMOVAL AND DISPOSAL 10 2 INSTALLATION 11 2 1 1 INSTALLATION CONDITIONS 11 2 1 2 POSITIONING...

Page 3: ...NING AND METHOD FOR USE 26 6 1 1 WORKING VERSION I 26 7 MAINTENANCE 29 7 1 1 CLEANING OR REPLACING FILTERS 29 7 1 2 CLEANING THE COOLER 29 7 1 3 GENERAL CLEANING UNIT 30 8 ALARMS 31 8 1 1 GENERALITY 3...

Page 4: ...ves the right to update products and manuals without any obligation to the previous update except in exceptional cases Contact the Sales Department of the manufacturer for further information or techn...

Page 5: ...k It warns that failure to observe the precaution may cause electric shock DANGER It warns that failure to observe the precaution may cause risk of injury to exposed persons WARNING It warns that fail...

Page 6: ...or on electrical panels any incomplete connection of the covers may cause overheating of the terminals Make sure that it meets the ground connection not to ground the appliance on the distribution pi...

Page 7: ...The unit is identifiable through the label on the front panel of the same lower On the package will be an additional nameplate with dell drive model and shipping references The plaque on the packaging...

Page 8: ...h painted externally is galvanized all indoor ofthe unit Structure perimetric self supporting in sheet metal galvanized There insulation of panels is realized with insulating to high performance of th...

Page 9: ...1 1 10 PACKING AND TRANSPORT The units are supplied to the transport fixed on a wooden pallet and inserted into cardboard boxes To facilitate travel units are equipped with a wooden pallet and the ho...

Page 10: ...ssors heat exchangers etc Keep anyway the unit horizontally without tilting All indications about the necessary precautions in order not occur made damage to the unit and the indication of the weight...

Page 11: ...the condensation water must be discharged not frozen at a certain inclination using a siphon not install the unit in areas with a high relative humidity such as the bathroom or toilet to avoid condens...

Page 12: ...direct contact with the walls to avoid possible noises from contact insert strips of rubber or neoprene in this case Ceiling mount Floor mounting For mounting unit on the ground is needed Position 4...

Page 13: ...exhaust condensation adhere to the following standards give a slope of at least 2 to the exhaust pipe provide for the possibility to disconnect the drain pipe for maintenance in particular in the cas...

Page 14: ...fferent applications and versions are always common to all units Make to respect the flows indicated on the plates input incoming water towards the unit output outgoing water from the unit Make so tha...

Page 15: ...haracteristics could affect the integrity of the hydraulic part of the the unit Check water quality DESCRIPTION Limit value Hardness 10 F PH value 7 5 9 Oxygen 2 mg l Conductivity 500 uS cm Iron 2 mg...

Page 16: ...tions are male threaded Observe the IN and OUT as the unit water inlet as a water outlet from the unit Connect the pipes with threaded female fitting and tighten with dedicated tools Be careful not to...

Page 17: ...r l Pag 17 N420229A_ManualHRW_rev2 en docx 4 1 3 2 3 WAY VALVE CONNECTION The connections of the valves to 2 3 Optional are to be made as indicated Attention to comply with the instructions placed on...

Page 18: ...ch take account of the compressor inrush currents as well as the maximum attainable load THE related data are indicated on the wiring diagram and on the unit nameplate E forbidden to enter the electri...

Page 19: ...Innova S r l Pag 19 N420229A_ManualHRW_rev2 en docx...

Page 20: ...ir quality regulator Contact closed active function CHILLER Chiller generators Activation Clean Contact Hot cold activation required N CL CP Water valve battery post Contact voltage 220v REMOTE DISPLA...

Page 21: ...t Closed alarm units ON OFF REMOTE for On Off control input units Closed unit ON SUMMER WINTER Input for change of digital input seasonal Closed units in summer FAN ONLY Input unit for forcing in vent...

Page 22: ...SION Link remote panel CNV The I Version tab provides a capacitive touch type remote control for the management of all functions of the unit and arranged for installation on wall or outer box 502 For...

Page 23: ...ORE the unit The CNV panel provides for the control of multiple units E can connect up to 30 units to be managed by the one remote control panel They will have to be connected in series connection wit...

Page 24: ...it OFF Contact open Unit ON CONNECTION TO ELECTRONIC CONTROL QUALITY AIR SQA E provided the connection of a regulator for the air quality of the digital type On the controller there are three levels o...

Page 25: ...umidity NB E can connect both the air quality regulator is the humidity regulator in parallel on the same terminals CONNECTION VALVE AFTER BATTERY The unit provides for the control of a valve battery...

Page 26: ...ity switch 3V Below are given the keys present on the main form Meaning of the main display keys Allows the ignition keyboard unit is turned off Button for changing the set temperature Keys for select...

Page 27: ...the speed the speed sensors The input is a digital input to connect a clean contact AUTO Function 6 1 1 4 CHANGING SEASON The change of season on the version I must be made from the keyboard Hold for...

Page 28: ...nualHRW_rev2 en docx 6 1 1 6 ADJUSTING BRIGHTNESS PANEL With Ignition is off hold down the button for 5 seconds until the written 01 With the button set the value to 00 and wait 20 seconds to verify t...

Page 29: ...he state of the heat exchanger at each cleaning exchange filters and proceed to its cleaning if deemed appropriate This operation must be performed only by qualified personnel installer To clean the h...

Page 30: ...n the case of ceiling installation disconnect the drain pipe open the cover by unlocking the fastening hooks on it proceed to the verification and eventual cleaning of the fans the condensate drain an...

Page 31: ...Outside temperature below 0 C The unit could be in antifreeze mode wait until the outside temperature rises or provide for the installation of an electric heater for pre heating Noise level high Noise...

Page 32: ...e and failure of the probe reading Check the connection of the probe or replace it NO LINK communication alarm Check the green LED on the board The LED indicates the presence of power on the card Chec...

Page 33: ...Innova S r l Pag 33 N420229A_ManualHRW_rev2 en docx 9 NOTES AND INFORMATION SERVICE NOTE...

Page 34: ...Innova S r l Pag 34 N420229A_ManualHRW_rev2 en docx 09 2017 rev 3 Technical Assistance Center The data contained herein may be modified by the manufacturer without notice...

Reviews: