OUTDOOR UNIT DISCHARGE 

GAS PIPE TEMPERATURE 

SENSOR FAILURE 

A. Connection location on outdoor unit main PCB 

is: 

CN15 PO\PG\PQ 

for 12kbtu/18kbtu/ 

24kbtu/36kbtu, PO is for outdoor ambient 

temperature sensor, PG is for outdoor fan coil 

temperature sensor, PQ is for outdoor unit discharge 

gas temperature sensor. Replace with new sensor; B. 

after step A, if unit still displays error code E07, 

change the outdoor unit main PCB. 

E08 

SINGAL COMMUNICATION 

BETWEEN INDOOR AND WIRE 

CONTROLLER FAILURE 

A.  Check  the  wiring  between  indoor  unit  and 

wire controller; B. If not work, change wire controller 

OR wire between wire controller and indoor unit PCB; 

C. if not work, change indoor unit PCB.   

 

09 

SINGAL COMMUNICATION 

BETWEEN INDOOR AND 

OUTDOOR UNIT FAILURE 

A. Check the wiring sequence between indoor unit 

and outdoor unit, if wired incorrect this will cause 

damage to the PCB for both indoor unit and outdoor 

unit; B. Check the status of LED4 lamp on outdoor 

unit main PCB, if it’s dark or flashing, check the 

wiring on outdoor unit main PCB, if wiring is 

correct, change the outdoor unit main PCB; C. if 

LED4 lamp is lit, change indoor unit PCB; D. If step 

C does not work, change outdoor unit main PCB. 

10 

DISCHARGE GAS TEMPERATURE 

OR COMPRESSOR 

TEMPERATURE OVERHEAT 

PROTECTION 

Check that the refrigerant charge is correct, if 

refrigerant charge is low test system for leaks. 

12 

INVERTER MODULAR BOARD 

FAILURE 

A. Check the voltage of input AC power is correct; 

B. Check the wiring on outdoor unit main PCB is 

correct, or loose; C. If step A & B are passed but 

unit is still not functional, change the inverter 

modular board; D. if step C does not work, then 

change the outdoor unit main PCB. 