DS 15.08 - GENII CS REM - Control Station Module

August 2013

Program Functions On The GENII CS Rem

Start Programming Mode

To enter Programming Mode depress and hold the 

 and 

ON

OFF

 buttons for 5 seconds. The display will become blank 

indicating that you are in the Programming Mode. Release both 

keys and the display will show parameter 0. 

Whilst in the programming mode the following buttons are 

active:

ON

OFF

 

Change to the next parameter.

 

Increase the current parameters value.

 

Decrease the current parameters value.

Parameter 0: Rem Address

The display will show current REM Address of the device.

•  The range of address is 0 to 15

•  The default address is 0

Parameter 1: Maximum Input Value

The display will show the Maximum Input Value to which the 

module’s input can be set.

•  The range of Maximum Input Value is 0.0 to 99.9

•  The factory default setting is 30.0

Parameter 2: Minimum Input Value

The display will show the Minimum Input Value to which the 

module’s input can be set.

•  The range of Minimum Input Value is 0.0 to 99.9

•  The factory default setting is 15

Exit Programming Mode

To exit the Programming Mode depress the 

ON

OFF

 and 

       

buttons and the new setting will be saved.

Start Up Default Settings

The GENII CS REM Module can be set to start in any mode of 

operation. 

1. To set the start up default adjust the GENII CS REM Module 

to the desired settings and then press and hold the 

ON

OFF

  

and 

 buttons for 5 seconds. 

2. The display will become blank indicating that the new 

settings are saved.

Operating Functions On The GENII CS Rem

Numerical Output

The GENII CS REM Module will display a 3 digit, single decimal place 

analogue output value during normal operation.

Numerical Input

The GENII CS REM Module will provide a 3 digit, single decimal place 

analogue input value to the GENESIS Controller during normal 

operation.

This value can be modified by pressing the 

 button to increment by 

0.1 or the 

 button to decrement by 0.1.

Digital Input Toggle Value

The 

ON

OFF

 button on the GENII CS REM Module provides a digital input 

value to the GENESIS Controller during normal operation. 

This operates as a standard toggle switch, i.e. Press the 

ON

OFF

 button 

once to change the state of the digital input. The state of the digital 

input value can also be changed by the Timer on the GENII CS REM 

Module.

Digital Output Led

The GENII CS REM displays a digital state via the system LED during 

normal operation.

Timer Operation

The Timer on the GENII CS REM Module allows for automatic toggling of 

the digital input value. 

Pressing the 

 button allows the timer to be set at a value from 

10 minutes to 24 hours. Successive pressing of the 

 button will 

increment the timer value until it reaches 24 hours, in which case it then 

resets to the value of 10 minutes. 

The timer LED indicates that the timer is active. When the timer value is 

reached the GENII CS REM Module will automatically toggle the digital 

input value. This has the same effect as the 

ON

OFF

 button being pressed 

manually

Summary of Contents for GENII CS REM

Page 1: ... to the GENESIS Controller There are no physical connections between field equipment and the GENII CS REM all input output values are edited and viewed on the wall unit The GENII CS REM may be located remotely from the GENESIS Digital Controller providing a distributed User Interface for the system The GENII CS REM is configured via the wallplate and programmed via the GEN2Config Software The GENI...

Page 2: ...ss must be set by programming Parameter 0 Please refer to the Program Functions section of this data sheet for more specific information regarding this Wiring The cable used for RS485 Comms must be shielded single twisted pair 120 ohms character impedence 36 to 45pF per metre capacitance between conductors The Comms cable must be organised as a bus topology That is starting at one end devices are ...

Page 3: ...ess and hold the ON OFF and buttons for 5 seconds 2 The display will become blank indicating that the new settings are saved Operating Functions On The GENII CS Rem Numerical Output The GENII CS REM Module will display a 3 digit single decimal place analogue output value during normal operation Numerical Input The GENII CS REM Module will provide a 3 digit single decimal place analogue input value...

Page 4: ...UTOR Australian Owned Designed Manufactured by Mass Electronics Brisbane Phone 61 7 3421 9100 Fax 61 7 3421 9101 Email sales innotech com au www innotech com au The INNOTECH device and the word INNOTECH are registered or unregistered trademarks of Mass Electronics Pty Ltd in Australia USA and other countries ...

Reviews: