INNO TCW-S1-UR2-230AC Operating Manual Download Page 5

Function: Sets cycle time for PID action.

22

Parameter

Min

Max

Fac.

1 sec 60 sec 3 sec

Cycle time also known as duty cycle, the total length of time for 

the controller to complete one ON/OFF cycle. 

Example  :

  With  a  20  second  cycle  time,  an  on  time  of  10 

seconds  and  an  OFF  time  of  10  seconds  represents  a  50 

percent  power  output. The  controller  will  cycle  ON  and  OFF 

while within the proportional band.

Function: Runs auto tunning.

21

Parameter

During auto-tuning, the AUTO icon is continuously ON.

This parameter will  be prompted only if selected control 

action is PID in           . 

This parameter is used to set YES/NO to start and stop  Auto-

tuning.

When Setting as       , the unit starts  auto-tuning. After 

Completing          is automatically Set.

Min

Max

Fac.

Sets the proportional band of PID parameter.

Min

Max

Fac.

O

0.1 C

O

100.0 C

O

10.0 C

Example :

 If the (SV-PV) error is large and positive, the control 

output will be proportionately large and positive and vice versa if 

error is negative.

Term P is proportional to the current value of the SV-PV error . 

Function: Sets proportional band.

23

Parameter

Parameter

Function: Sets integration time.

24

Sets the integration time of PID parameter.

Min

Max

Fac.

0 sec 2000 sec 120 sec

Term I accounts for past values of the SV-PV error and 

integrates them over time to produce the I term. 

Setting "0" will turn OFF integration.

Example :

 If there is a residual SV-PV error after the 

application of proportional control, the integral term seeks to 

eliminate the residual error by adding a control effect due to 

the historic cumulative value of the error. 

Function: Set the hysteresis width for ON-

OFF action in Control1.

26

Parameter

Min

Max

Fac.

O

1 C

O

100 C

O

2 C

This parameter will be prompted only if selected control action 
is       (reverse) or       (forward) in          setting.
It sets the deadband between ON & OFF switching of the 
output.

O

Example (For Fd control) : 

If the set point is set at 100 C and 

O

O

hysteresis is set at 2 C, then when the system reaches 100 C, 

O

the heater relay will go OFF. Since the hysteresis is 2 C, the 

O

O

O

heater relay will get ON (restart) at 102 C (100 C +2 C).

Function: Sets differential time.

25

Parameter

Sets the differential time of PID parameter.

Setting "0" will turn OFF differential.

Term D is a best estimate of the future trend of the SV-PV error, 

based  on  its  current  rate  of  change.  It  is  sometimes  called 

"anticipatory control", as it is effectively seeking to reduce the 

effect  of  the  SV-PV  error  by  exerting  a  control  influence 

generated  by  the  rate  of  error  change.  The  more  rapid  the 

change, the greater the controlling or dampening effect.

Min

Max

Fac.

0 sec 1000 sec 30 sec

Function: Sets control action for 

relay1/SSR.

20

This parameter is used to set required control action for 

relay 1/SSR as,

Parameter

28

Parameter

Function: To lock keypad.

         = unlocked parameter
         = Locked parameter
When locked all parameters can only be viewed ,but can not 
be modified.

This parameter is used to lock the parameter so that 
tampering is not possible by by-standers.

Min

Max

Fac.

Function: Sets Control1 output.

27

Parameter

User has to set this parameter in accordance with the output 

used.

This parameter is used to configure          out as,

       = SSR

       = Relay 

Min

Max

Fac.

= Reverse

= Forward

= PID

Min

Max

Fac.

LEVEL2 Parameter

Press the         key to save the set value and to come out of 

parameter setting after changing the set value. 

           will flash.

Press  &  hold          key  for  6  seconds  to  enter  into  Level2 

parameter setting(            will flash). When release the key, 

Press 

UP/DOWN

 keys to modify the set value and to go to the 

next parameter by pressing        key.

LED Indication

LED

Description

Status

ON

OFF

Relay1 / SSR OFF.

Relay1 / SSR ON.

ON

OFF

Relay2 OFF.

Delay timer is running.

Relay2 ON.

ON

OFF

Tuning is in progress.
Tuning Stop. 

FLASHING

FLASHING

ON

Dwell time elapsed.

Dwell timer is in progress.  

Alarm relay ON.

 Alarm Relay OFF.

ON

OFF

ON

OFF

Parameters are Locked.      
Parameters are Unlocked.

OFF

Dwell timer disabled. 

ON

Alarm indication ON.

 

OFF

Alarm indication OFF.

 

Min

Max

Fac.

2.4

9.6

38.4

Disclaimer:

 This manual & its contents remain the sole property of  

INNO Automation

 

. India and shall not be reproduced or distributed 

without  authorization. Although  great  care  has  been  taken  in  the 

preparation of this document, the company or its vendors in no event 

will be liable for direct, indirect, special, incidental or consequential 

damage  arising  out  of  the  use  or  inability  to  use  the  product  or 

documentation, even if advised of the possibility of such damages. 

No part of this manual may be reproduced or transmitted in any form 

or by any means without the prior written permission of the company. 

INNO Automation  reserves  the  right  to  make  and  changes  or 

improvements without prior notice.

Warranty:

 This product is warranted against defects in materials and 

workmanship for a period of one year from the date of purchase. 
During the warranty period, product determined by us to be defective 
in form or function will be repaired or, at our option, replaced at no 
charge.  This  warranty  does  not  apply  if  the  product  has  been 
damaged by accident, abuse, and misuse or as a result of service or 
modification other than by the company. This warranty is in lieu of any 
other warranty expressed or implied. In no event shall the company 
be held liable for incidental or consequential damages, including lost 
revenue or lost business opportunity arising from the purchase of this 
product.

Calibration Certificate

DATE

MODEL NO.

 

 

  (20 min of settling time for TC inputs)

Claimed Accuracy :

For TC inputs  :  0.3% of FS

For Analog inputs : 0.3% of FS

O

For RTD inputs  :  0.1% of FS +/-1 C

Calibration Instrument & Sr. No :

Calibrated ON     : 
Valid Upto  

  :

The calibration of this unit has been verified at the following 

values :

Instrument is confirmed accepted as accuracy is within the 

specified limit. This certificate is valid upto one year from the 

date of  issue.

CONTROLLER

SR. NO.

Checked By :

INNO Automation, Chennai-600032

(Specification are subject to change, since development is a 

continuos process.)

SENSOR TYPE

RTD

VALUE 

O

TESTED ( C)

O

0 C

O

100 C

O

350 C

J,K

Analog

O

50 C

4 mA

O

400 C

12 mA

O

650 C

20 mA

VALUE 

O

Observed ( C)

All values 

within 

specified 

limit of 

accuracy

Error Messages

Message

Description

Displays when input sensor is disconnected 

or sensor is not connected.

Flashes when measured value is higher 

than input range.
Flashes when measured value is lower 

than input range.

temperature limit.

Temperature above the maximum high

temperature limit.

Temperature below the minimum low

=

=

=

=

=

=

=

=

=

Alarm Types

Setting

Alarm Type

Description

Deviation high limit alarm

Deviation low limit alarm

Absolute value high limit 

alarm

Absolute value low limit 

alarm

 *

         : Alarm output hysteresis

High temperature alarm

Low temperature alarm

Alarm OFF when PV = SV

SV =           +

FD Alarm ON when PV < SV - 

Alarm OFF when PV = SV

SV =           +

FD Alarm ON when PV > SV + 

Alarm ON when PV < SV - 

SV =

Alarm OFF when PV = SV  

Alarm OFF when PV = SV

SV =  

 Alarm ON when PV > SV + 

PV >  

PV <

=

=

=

(Message on display)

Useful to debug setting related problems.

19

Parameter

Function : To restore default settings of 

the controller.

When Set to        all parameter are programmed to factory 

values.

Min

Max

Fac.

Function: Set the hysteresis for ON-OFF 

action for Relay2.

15

Min

Max

Fac.

O

1 C

Parameter

O

100 C

O

2 C

It  sets  the  deadband  between  ON  &  OFF  switching  of  the 

output.

This parameter will be prompted only if selected control action 

is rE (reverse) or Fd (forward) in          setting.

O

Example (For Fd control) : 

If the set point is set at 100 C and 

O

O

hysteresis is set at 2 C, then when the system reaches 100 C, 

O

the heater relay will go OFF. Since the hysteresis is 2 C, the 

O

O

O

heater relay will get ON (restart) at 102 C (100 C +2 C).

Note:

  For  4-20  Input,  as  per  rSCL  decimal  point  will  be 

selected. 

Function: Sets the alarm type. 

17

      (forward).

It's applicable when           action is      (reverse) or

: Deviation

: Absolute

Parameter

For alarm types setting , please 

refer Alarm Type description.

Min

Max

Fac.

18

Type of alarm can selected by using           parameter.

Set "      " to enable AL1 icon.

AL1 icon turns ON when the corresponding alarm output 

turns ON.

Parameter

Function: Sets AL1 icon as alarm relay 

ON/OFF indicator for alarm indication. 

Min

Max

Fac.

Function: Input value scaling point 1. 

11

Parameter

To set the lower value of the analog input signal. 

This parameter is prompted when input is selected as 4-20.

 Parameter

Function: To set maximum allowable high 

temperature limit. 

9

O

Example: 

If  this  parameter  is  set  to  700 C  and  the 

O

temperature reaches or goes above 700 C, display will show

      (High  Temp.)  alarm  indicating  that  the  temperature  has 

reached or gone above the value set in this parameter.

(Message on display)

Note : Ht fault will be ignored at every power ON.

 Parameter

Function: To set minimum allowable low 

temperature limit. 

10

O

Example: 

If this parameter is set to -40 C and the temperature 

O

reaches or goes below -40 C, display will show      (Low temp) 

alarm  indicating  that  the  temperature  has  reached  or  gone 

below the value set in this parameter.

Note : Lt fault will be ignored at every power ON.

Function: Sets the lower limit of PV input.

8

Parameter

Min

Max

Fac.

Once set at a particular value, this will not allow the set point 

to go below  this value.

O

-50 C

For J type sensor

When changing the setting value and SV < LSV, SV is reset 

as LSV.

Sets the minimum limit for set point adjustment. It can be set 

from minimum specified range of selected sensor to HSV-1 

value.

O

-50 C

    

- 1

Min

Max

Fac.

4 mA

4 mA

Function: Input value scaling point 2. 

12

Parameter

This parameter is prompted when input is selected as 4-20.

To set theupper value of the analog input signal. 

Min

Max

Fac.

20 mA

20 mA

Function: To set reverse scaling for 

analog input. 

13

Parameter

Min

Max

Fac.

Function: Sets control action for relay2.

14

This parameter is used to set required control action for 

relay 2 as,

Parameter

= Off
= Reverse
= Forward
= Dwell time

Reverse  scaling  for  analog  input  is  achieved  when  this 

parameter is set to “       ”.

Example:

 For 4mA input display will show 9999 and for 20mA 

input display will show -1999.

Function: To set time delay between 

output relay restart. 

16

Parameter

Min

Max

Fac.

1200 

Sec

0 Sec

0 Sec

Use UP/DOWN keys to set desired value.

Example

: If this parameter is set to 60 Sec, Output 2 relay 

goes OFF at the set point, it will not restart until time delay 

completes, even if differential is achieved earlier. 

This  parameter  is  used  to  protect  the  output  device  from 

restarting in a short period of time.

Note: 

If set to 0, dly parameter will be ignored.

Min

Max

Fac.

Min

Max

Fac.

LEVEL3 Parameter

Press & hold         key for 8 seconds to enter into  

 parameter setting(            will flash). When release the key, 

        will flash.

Press 

UP/DOWN

 keys to modify the set value and to go to the 

next parameter by pressing        key.

Press the         key to save the set value and to come out of 

parameter setting after changing the set value. 

29

Parameter

Function: To set device Id.

To communicate properly controller 
side and PC side Id should match. 

Min

Max

Fac.

1

1

255

30

Parameter

Function: To set baud rate for communication. 

To communicate properly controller side and PC side baud rate 
should match. 

Range:

 2400,4800,9600,19200,38400 

Note:

  For  4-20  Input,  as  per  rSCL  decimal  point  will  be 

selected. 

Min

Max

Fac.

Reviews: