ITC-308 User Manual
Inkbird Tech. Co., Ltd. www.ink-bird.com
9
When measured temperature is lower or equal to AL, low temperature alarm will be
triggered, buzzer will alarm with tone “bi-bi-Biii” until the temperature >AL or any key is
pressed.
5.3 Compressor Delay (PT)
Under refrigeration mode, after power on, if the measured temperature is higher than the
value of setting temperature(TS) plus cooling differential(CD), the equipment won’t start
refrigeration immediately, but waiting for a delay time.
When the time interval between two refrigeration operation is larger than preset delay, the
equipment will start refrigeration immediately; when the time interval between two
refrigeration is less than preset delay, the equipment won’t start refrigeration until preset
delay is satisfied.
Delay time will be calculated right after the moment refrigeration stops.
5.4 Temperature Calibration (CA)
When there is deviation between measured temperature and actual temperature, use
temperature calibration function to align the measured temperature and actual
temperature. The corrected temperature is equal to temperature before calibration plus
corrected value(corrected value could be positive value, 0 or negative value
)
.
5.5 Display in Fahrenheit or Centigrade unit (CF)
Users can select display with Fahrenheit or Centigrade temperature value according to
their own habit. Default setting is display with Centigrade temperature value. For
displaying with Fahrenheit temperature value, set CF value as F.
Attentions: when CF value changed, all the setting value will be recovered to factory
settings.