82
Ingeteam Energy, S.A.
AAV2000IKI01
Installation manual
10. Configure the can number.
11. Configure the node number.
8.6. Replacing varistors in the intake board
The varistor is connected to the 3-pin connector on pins 1 and 2. Pin 3 is for connecting the thermal fuse.
The varistor must be connected as follows:
•
Check continuity of the fuse with the varistor outside the board using the tester.
•
Place the varistor on the board in position 1-2 varistor, 2-3 fuse.
Transformers
Inserting the varistor back-to-front will destroy it.