Fmin (81<.S2)
Lowest lower limit of the frequency protection.
Vmax (59.S1)
Lowest upper limit of the voltage protection.
Vmax (59.S2)
Highest upper limit of the voltage protection.
Vmin (27.S2)
Lower limit of the voltage protection.
There are three different states:
Non eseguito
No autotest running and none has been performed during the time in which the inverter has
been switched on.
Riconnessione
State awaiting reconnection for the next measurement after an Fmax, Fmin, Vmax or Vmin
check.
Completato
A full autotest has been carried out during the time in which the inverter has been switched on.
Press
on
Avviare Autotest
to start autotest. Access
Risultati
to consult the results of the different tests,
observing whether the result is correct or incorrect. An autotest can be stopped when running by pressing
on
Eseguire Autotest
.
The results screens for an autotest are then displayed if the test has been completed and a second case in which
the test has not been completed:
4/30/2015
10:17 AM
4/30/2015
10:17 AM
4/30/2015
10:17 AM
4/30/2015
10:17 AM
Autotest complete, correct result
Autotest not complete, no result
12.6.6. Advanced settings
The settings included within this menu can only be modified by a qualified installer.
Ingeteam accepts no liability for incorrect use of the installer password nor the consequences that
may arise from incorrect configuration of the unit by the user and / or the installer.
To modify the parameters of this menu the installer password will be requested.
The installer password is 3725.
Within this menu you can change the password, adjust the voltage and frequency values or modify the country and
the regulations applicable to the inverter.
12.6.7. Inverter data
From this menu you can consult different data referring to the inverter.
82
Display control
Ingeteam
ABE2011IQM01_B - Installation and Operation Manual
Summary of Contents for INGECON SUN 1Play 2.5TL
Page 48: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 90: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 132: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 258: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 260: ...Ingeteam Power Technology S A www ingeteam com ABE2011IQM01_B 04 2015...