Preface

The Automatic Transfer Switch (hereafter referred to as ATS) uses world-famous ATS or AC Contactors as 
the main switches, and are manufactured from advanced and closely-controlled production processes.  It is 
combined with all our automatic generators to form a complete and thorough Automatic Transfer System.

The DKG-173 Transfer Controller is installed inside the ATS, which applies to three phase or single phase 
systems with phase voltage of 220v AC.  Pluggable connectors are connected with external connections, which 
make the maintenance, inspection, or replacement easy and convenient.

We have 125A single phase ATS, 125A three phase ATS, and 200A single phase ATS for your different needs in 
various conditions.

Functions

ATS has control functions (such as generator start-up delay, mains restore delay and voltage 
 detection, etc.).  When the ATS is connected to automatic generators, the generator's control 
box will send the transfer signal in order to transfer loads automatically.  It can operate with our automatic 
control systems or other brands that have remote-start self-control functions which are simple and economic.

Control Mode
Generation/Automatic/Mains

LED Display
Mains Available
Mains on Load
Generator Available
Generator on Load

Parameter Settings
  M. VOLT. SET: Mains Voltage Normal Value Setting, 75%-100% settable
  VOLT. 100% = 170-300V
  MCT: Closing Delay Time afer Mains Voltage returns to normal, 0-40 MIN. settable
  GCT: Closing Delay Time after Generator Voltage returns to normal, 0-40S settable
  G. VOLT. SET: Generator Voltage Normal Value Setting, 75%-100% settable
  VOLT. 100% = 170-300V
  Protection Function: Mains/Generator low voltage protection

3

18-SG01D1-1A-EN

Summary of Contents for Trane TR15REG-DB

Page 1: ...B 20Kw single phase o TR20REG DB 3 20Kw three phase Note Graphics in this document are for representation only Actual model may differ in appearance March 2017 18 SG01D1 1A EN Installer s Guide Home S...

Page 2: ...g 7 Specifications 8 DKG 173 Controller 9 DKG 173 Specifications 10 Application Rang 11 Typical Connection Diagram 12 Relevant Models and Implications 13 Product Appearance and Parts Description 14 MC...

Page 3: ...as control functions such as generator start up delay mains restore delay and voltage detection etc When the ATS is connected to automatic generators the generator s control box will send the transfer...

Page 4: ...serve them carefully Their definitions are as follows DANGER After this heading read instructions that if not strictly complied with will result in personal injury or property damage WARNING After thi...

Page 5: ...witch is designed for use only with Trane home standby generator sets Install the transfer switch as close as possible to the electrical loads that are to be connected to it Mount the switch verticall...

Page 6: ...Generator Available indicator lights up If the ATS automatically switches the generator on and the Generator On Load indicator lights up 5 When the utility is restored the Mains Available indicator li...

Page 7: ...tly connected especially the mains power source the generator power source and load lines C Check if the control lines from the ATS to the Control Box are correctly connected 2 Indicators do not work...

Page 8: ...C Remote start relay output 10A 250V AC 28V DC Operation temp range 30 C 22 F to 70 C 158 F Storage temp range 30 C 22 F to 80 C 176 F Max Humidity 95 non condensing non condensation Size 70 x 115 x 6...

Page 9: ...uired Adjustable MCB and GCB delays 10A 250V AC MCB and GCB outlets 10A 28V DC 250V AC remote start output Isolated mains and generator set inputs OPERATION When the mains exist while all its phase vo...

Page 10: ...ains voltage present MC mains contactor closed Technical Specifications Alternator voltage 170 300V AC Ph N Mains Voltage 170 300V AC Ph N Generator contactor delay 1 to 40 seconds adjustable Mains re...

Page 11: ...er to meet the assembly lines etc in order to meet the requirements of providing more reliable power sources The products are characterized by its small size easy operation fast switching speed and hi...

Page 12: ...Typical Connection Diagram 12 18 SG01D1 1A EN...

Page 13: ...ated Voltage Wiring Method Control Voltage MCQ3 three segments with open position 20 40 80 100 2 2 poles 690V F Front 2 230V AC MCQ2 double segments without open position 125 160 200 225 3 3 poles 400...

Page 14: ...Product Appearance and Parts Description 14 18 SG01D1 1A EN...

Page 15: ...A AC100V 110V 1A 1 5A 2A AC200V 220V 0 5A 0 7A 1A Perfor mance Short time Withstand Current 5KA 10KA 12KA 15KA Rated Conditional Short Circuit Current 12 5KA 25KA 30KA 37 5KA Connecting and Breaking C...

Page 16: ...KA 35KA 50KA 50KA 50KA Rated Conditional Short Circuit Current 50KA 55KA 55KA 80KA 100KA 120KA Connecting and Breaking Capa bility AC 33B 10Ie Connect 8Ie break cos 0 35 DC 33B 1 1Ie Connect 1 1Ie Bre...

Page 17: ...itional Short Circuit Current 12 5KA 25KA Connecting and Breaking Capability AC 33B 10Ie connect 8Ie break cos 0 35 DC 33B 1 1Ie connect 1 1Ie break L R 1ms Switching Time A power side Control 55ms Br...

Page 18: ...m 690V 160A 250A Panel Safe Distance S1 Dimensions 30mm 400V 60mm 690V 18 18 SG01D1 1A EN 1 Operation Circuit Terminal 2 Manual Operation Handle Entrance 3 Auxiliary Switch 4 A Power Side Main Circuit...

Page 19: ...Installation Dimensions 19 18 SG01D1 1A EN...

Page 20: ...200 360 360 360 360 360 420 420 420 420 J 2P 145 145 180 180 225 285 310 460 460 3P 210 210 260 260 325 420 455 690 690 4P 275 275 340 340 425 600 600 920 920 K 330 330 330 330 330 350 350 350 350 L 2...

Page 21: ...using manual operation method if possible Please operate as the following instructions if the manual operations are unavoidable 1 Completely no operation power supply 2 When checking on operation mec...

Page 22: ...Typical Connection Diagram 22 18 SG01D1 1A EN...

Page 23: ...ATS Single Phase Connection Diagram 23 18 SG01D1 1A EN...

Page 24: ...ATS Three Phase Connection Diagram 24 18 SG01D1 1A EN...

Page 25: ...ATS Three Phase Exploded Diagram 25 18 SG01D1 1A EN...

Page 26: ...ATS Single Phase Exploded Diagram 26 18 SG01D1 1A EN...

Page 27: ...ATS Single Phase Installation Diagram 27 18 SG01D1 1A EN...

Page 28: ...ATS Three Phase Installation Diagram 28 18 SG01D1 1A EN...

Page 29: ...Parts List 29 18 SG01D1 1A EN...

Page 30: ...ATS Control Box Installation Hole Diagram 30 18 SG01D1 1A EN...

Page 31: ...Contactor C1 Solenoid Coil utility closing C2 Solenoid Coil standby closing TR Relay Transfer TB Terminal Strip customer connection XA1 XB1 Limit Switches Actuator F1 F2 F3 F4 Fuse 5a VR1 VR2 Varisto...

Page 32: ...ATS Three Phase Connection Schematics 32 18 SG01D1 1A EN...

Page 33: ...ATS Three Phase Connection Diagram 33 18 SG01D1 1A EN...

Page 34: ...ATS Single Phase Connection Diagram 34 18 SG01D1 1A EN...

Page 35: ...ge etc 3 External injury or damage due to drop or impact 4 Natural hazards or abnormal disasters such as earthquake fire thunder strike and abnormal voltage etc Note Do not install in environments whe...