Ingersoll-Rand Trane CALMAC Ice Bank Operation & Maintenance Manual Download Page 3

In a standard installation, ice is made at night. The 
water-glycol solution circulates through the chiller and 
the Ice Bank® heat exchanger, bypassing the air handler 

(-3.9ºC) and the water surrounding the heat exchanger 
freezes.

During  the day,  the  glycol  solution  is  cooled  by  the 
IceBank® tank from approximately 52ºF to 34ºF (11ºC to 
1ºC). (See Figure 3). A temperature modulating valve is 
used to maintain a blended supply temperature typically 

-

it cools air ordinarily from 75ºF to 55ºF (24ºC to 13ºC). 

chiller and is cooled to 52ºF (11.1ºC). In some systems, 
the ice will handle the entire day time load (Full Storage) 
and in others, the ice will help a smaller than full size 
chiller meet the load (Partial Storage).

MAINTENANCE

Since there are no moving parts in our standard thermal 
storage tanks, the list of maintenance items is short. The 
items  we  do  list are  important  and  should  be  done  at 
regular intervals as indicated. The inspection port cover 
must always be replaced.

Water Level

The water level in the tank will rise and fall 2.5 to 7.8 
inches  (63 to  195mm)  (depending  on  Model  No.  of 
tank) during the charge and discharge cycle. This change 

Water expands approximately 9% when changing to ice 
at  32ºF (0ºC);  therefore,  during  the freezing  process, 
the  level  will  rise.  (More  about  this  in  later  sections). 
The water stays in the tank (it is NOT pumped through 
the  system)  and  the  amount  of  water/ice  in  the  tank 
remains constant except for possibly a slight amount of 
evaporation, which normally occurs in outdoor, very hot, 
dry climates.

The  water  level  should be  just covering  the top  heat 
exchanger  tube,  (which  is 

5/8

"  (16mm)  diameter  and 

the bottom of the top HX tube. This measurement must 
be done with no ice in the tank. The water level should 
be checked every year except in hot, dry climates when 
every three months is recommended.

Inventory Meter Calibration

During operation the only time to accurately check that 
the  the  inventory  meter probe  level  is  correct  is  when 
the  tank  is  100%  charged.  (See Ice  Inventory Meter 
Manual IB-153 for more information.) 

Coolant Concentration

The coolant should be checked regularly in accordance 
with  the  manufacturer’s  recommendations. For  eth-

a  sample  should  be  sent  once  a  year to  the  manufac-
turer for  analysis.  Checking  the coolant’s freeze  point 
is  recommended  twice a  year  using a refractometer  or 

The maximum freezing point for our system is normally 
12ºF  (-11.1ºC)  (25%EG/H2O); however,  some  jobs 
require lower freeze points because of particular oper-
ating conditions.

Storage Tank Water Treatment

Pour  in  the initial treatment  of  biocide  into  the  tank 

partially frozen  year round, provide retreatment  with 
biocide as needed. However, if tanks are not kept frozen 

the tanks should be checked for slime or odor season-
ally. At the end of the cooling season, you should fully 
charge the tanks and leave them frozen until the start of 
your next air-conditioning season. This will help to con-
trol  biological growth.  CALMAC®  recommends a  20% 
Tetrakis  hydroxymethyl  phosphonium  sulfate  solution 
such as Aquacar PS20. All tank models require 16 oz. of 
biocide solution per tank.

The CAS number is 555-66-30-8

In most systems, the termination of the charge cycle is 
determined  by  the temperature of  the coolant  leaving 
the storage  tanks. Typically  this temperature  is  in  the 
range of 27-28ºF (-2.7 to -2.2ºC). However, it is imper-
ative that the actual temperature be calculated for each 
system using CALMAC Performance Data (IB-102).

This temperature  is  calculated  by  adding  Coolant 
Temperature  Rise to  the  minimum Charging  Coolant 
Temperature. This temperature should be entered in the 

and checked once every six months.

Reviews: