Electrical Data
14
ACC-SVN67H-EN
Table 5.
Unit wiring with electric heat (single point connection) - standard efficiency
Tons
Unit Model
Number
Heater Model
Number
Heater kW
Rating
(a)
Control
Stages
Standard Indoor Motor
Oversized Indoor Motor
MCA
Max Fuse Size or
Max Circuit
Breaker
MCA
Max Fuse Size or
Max Circuit
Breaker
208/230 Volts Three Phase
6
WSC072E3
BAYHTRW309*
6.8/9.0
1
59.8/63.4
70/80
61.1/64.7
70/80
6
WSC072E3
BAYHTRW318*
13.5/18.0
1
83.2/90.4
90/100
84.5/91.7
90/100
6
WSC072E3
BAYHTRW327*
20.3/27.0
2
106.7/117.6
110/125
108.0/118.9
110/125
6
WSC072E3
BAYHTRW336*
27.0/36.0
2
130.2/144.6
150/150
131.5/145.9
150/150
7.5
WSC090E3
BAYHTRU309*
6.8/9.0
1
61.9/65.5
80/80
67.7/71.3
80/90
7.5
WSC090E3
BAYHTRU318*
13.5/18.0
1
85.2/92.5
100/100
91.0/98.3
100/100
7.5
WSC090E3
BAYHTRU327*
20.3/27.0
2
108.7/119.6
110/125
114.5/125.4
125/150
7½
WSC090E3
BAYHTRU336*
27.0/36.0
2
132.2/146.6
150/150
138.0/152.4
150/175
10
WSC120E3
BAYHTRB318*
13.5/18.0
1
98.8/106.1
100/110
—/—
—/—
10
WSC120E3
BAYHTRB327*
20.3/27.0
2
122.3/133.2
125/150
—/—
—/—
10
WSC120E3
BAYHTRB336*
27.0/36.0
2
145.8/160.2
150/175
—/—
—/—
10
WSC120E3
BAYHTRB354*
40.6/54.0
2
192.7/181.8
200/200
—/—
—/—
460 Volts Three Phase
6
WSC072E4
BAYHTRW409*
9.0
1
33.8
40
34.4
40
6
WSC072E4
BAYHTRW418*
18.0
1
47.4
50
48.0
50
6
WSC072E4
BAYHTRW427*
27.0
2
60.9
70
61.5
70
6
WSC072E4
BAYHTRW436*
36.0
2
74.4
80
75.0
80
7.5
WSC090E4
BAYHTRU409*
9.0
1
32.5
40
35.4
40
7.5
WSC090E4
BAYHTRU418*
18.0
1
46.1
50
49.0
50
7.5
WSC090E4
BAYHTRU427*
27.0
2
59.6
60
62.5
70
7.5
WSC090E4
BAYHTRU436*
36.0
2
73.1
80
76.0
80
10
WSC120E4
BAYHTRB418*
18.0
1
53.2
60
—
—
10
WSC120E4
BAYHTRB427*
27.0
2
66.7
70
—
—
10
WSC120E4
BAYHTRB436*
36.0
2
80.2
90
—
—
10
WSC120E4
BAYHTRB454*
54.0
2
91.1
100
—
—
575 Volts Three Phase
6
WSC072EW
BAYHTRWW18*
18.0
1
34.0
35
34.9
35
6
WSC072EW
BAYHTRWW27*
27.0
2
44.9
45
45.8
50
6
WSC072EW
BAYHTRWW36*
36.0
2
55.6
60
56.5
60
7.5
WSC090EW
BAYHTRUW18*
18.0
1
36.1
40
38.1
40
7.5
WSC090EW
BAYHTRUW27*
27.0
2
47.0
50
49.0
50
7.5
WSC090EW
BAYHTRUW36*
36.0
2
57.7
60
59.7
60
10
WSC120EW
BAYHTRBW18*
18.0
1
42.7
45
—
—
10
WSC120EW
BAYHTRBW36*
36.0
2
64.4
70
—
—
10
WSC120EW
BAYHTRBW54*
54.0
2
73.1
80
—
—
(a) The standard motor for the 1-phase models is a multispeed, direct drive motor. The standard motor for 3-phase models (10 ton) is a multispeed, direct
drive motor. The standard motor for 3-phase (6 to 7.5 tons) is a belt drive motor.
Summary of Contents for Precedent BAYHTRA309
Page 19: ......