RT-SVF25C-EN

13

Electrical Data

Table 13. Unit wiring - standard efficiency

Standard Indoor Fan Motor

(a)

Oversized Indoor Fan Motor

Tons

Unit Model

Number

Voltage

Range

MCA

Max Fuse Size 

or Max Circuit 

Breaker

MCA

Max Fuse Size 

or Max Circuit 

Breaker

6

T/YSC072F3

187-253

36.5

50

37.8

60

6

T/YSC072F4

414-506

18.2

25

19.4

25

6

T/YSC072FW

517-633

12.7

20

13.5

20

(a) Belt Drive Motor.

Table 14. Unit wiring with electric heat (single point connection) - standard efficiency

 

Standard Indoor Motor

(a)

Oversized Indoor Motor

Tons

Unit Model

Number

Heater Model 

Number

Heater kW 

Rating

Control 

Stages

MCA

Max Fuse Size or 

Max Circuit 

Breaker

MCA

Max Fuse Size or 

Max Circuit 

Breaker

208/230 Volts Three Phase

6

TSC072F3

BAYHTRS309*

6.8/9.0

1

36.5/36.5

50/50

37.8/37.8

60/60

6

TSC072F3

BAYHTRS318*

13.5/18.0

1

53.1/60.4

60/70

54.8/62.0

60/70

6

TSC072F3

BAYHTRS327*

20.3/27.0

2

76.6/87.5

80/90

78.3/89.1

80/90

6

TSC072F3

BAYHTRS336*

27.0/36.0

2

100.1/114.5

110/125

101.8/116.1

110/125

460 Volts Three Phase

6

TSC072F4

BAYHTRS409*

9.0

1

18.2

25

19.3

25

6

TSC072F4

BAYHTRS418*

18.0

1

30.3

35

31.6

35

6

TSC072F4

BAYHTRS427*

27.0

2

43.8

45

45.1

50

6

TSC072F4

BAYHTRS436*

36.0

2

57.3

60

58.6

60

575 Volts Three Phase

6

TSC072FW

BAYHTRSW09*

9.0

1

13.0

20

14.0

20

6

TSC072FW

BAYHTRSW18*

18.0

1

23.8

25

24.8

25

6

TSC072FW

BAYHTRSW27*

27.0

2

34.6

35

35.6

40

6

TSC072FW

BAYHTRSW36*

36.0

2

45.4

50

46.4

50

(a) Belt Drive Motor.

Table 15. Electrical characteristics - compressor motor and condenser motor - 60 cycle - standard efficiency

Compressor Motors

Condenser Fan Motors

Unit Model

Amps

(a)

Amps

(

a

)

Tons

Number

No.

Volts

Phase hp

(b)

rpm

RLA

LRA

No.

Volts

Phase

hp

FLA

LRA

6

T/YSC072F3

1

208-230

3

5.6

3500

22.4

149.0

1

208-230

1

.70

3.5

10.9

6

T/YSC072F4

1

460

3

5.6

3500

10.6

75.0

1

460

1

.70

2.4

6.6

6

T/YSC072FW

1

575

3

5.6

3500

7.7

54.0

1

575

1

.70

1.4

3.6

(a) Amp draw for each motor; multiply value by number of motors to determine total amps.

(b) hp for each compressor.

Summary of Contents for TSC072F Series

Page 1: ...ning Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on...

Page 2: ...ates a potentially hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could res...

Page 3: ...mission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks...

Page 4: ...omizer 17 Economizer Set Up 17 ReliaTel Control Heating Operation for Cool ing Only Units 17 ReliaTel Control Heating Operation for Gas Units 17 Ignition Module 17 Drain Pan Condensate Overflow Switch...

Page 5: ...t Btu 2 3 3 No Stages Low Heat Input Btu Mid Heat Input Btu High Heat Input Btu 1 1 2 Gas Supply Line Pressure Natural minimum maximum LP minimum maximum 4 5 14 0 11 0 14 0 Gas Connection Pipe Size in...

Page 6: ...14 1037 1 22 1068 1 30 1097 1 38 1127 1 47 1154 1 55 1182 1 64 1210 1 74 2160 957 1 12 991 1 21 1024 1 30 1057 1 40 1087 1 49 1117 1 58 1146 1 67 1174 1 76 1201 1 85 1227 1 95 2400 980 1 27 1013 1 37...

Page 7: ...r Drive 1920 990 1 05 1026 1 14 1062 1 24 1096 1 33 1130 1 43 1160 1 52 1190 1 61 1218 1 71 1247 1 80 1273 1 90 2160 1010 1 21 1047 1 31 1082 1 40 1116 1 50 1150 1 61 1182 1 71 1211 1 81 1242 1 92 127...

Page 8: ...or Drive 1920 941 0 99 977 1 07 1009 1 15 1041 1 23 1073 1 32 1103 1 40 1132 1 49 1159 1 57 1187 1 66 1213 1 75 2160 964 1 13 997 1 23 1031 1 32 1061 1 41 1093 1 50 1123 1 60 1151 1 69 1179 1 78 1207...

Page 9: ...996 1 06 1033 1 16 1067 1 25 1102 1 35 1134 1 44 1165 1 53 1195 1 63 1223 1 72 1251 1 82 1277 1 91 2160 1018 1 23 1054 1 32 1090 1 42 1123 1 52 1156 1 63 1188 1 73 1218 1 84 1247 1 94 1276 2 05 1304...

Page 10: ...Kit or 2 hp Oversized Motor Drive 1920 963 1 04 997 1 12 1028 1 20 1061 1 28 1090 1 36 1119 1 45 1149 1 54 1177 1 63 1203 1 71 1229 1 80 2160 990 1 21 1023 1 30 1055 1 39 1086 1 48 1115 1 57 1144 1 6...

Page 11: ...20 1018 1 12 1054 1 21 1089 1 31 1122 1 40 1154 1 50 1184 1 59 1212 1 69 1241 1 78 1268 1 88 1293 1 97 2160 1045 1 30 1081 1 40 1114 1 50 1149 1 61 1181 1 71 1211 1 81 1241 1 92 1270 2 03 1298 2 13 13...

Page 12: ...both ReliaTel and Electromechanical controls Table 11 Outdoor sound power level dB ref 10 12 W Unit Model Octave Center Frequency Overall Tons Number 63 125 250 500 1000 2000 4000 8000 dBA 6 T YSC072F...

Page 13: ...6 87 5 80 90 78 3 89 1 80 90 6 TSC072F3 BAYHTRS336 27 0 36 0 2 100 1 114 5 110 125 101 8 116 1 110 125 460 Volts Three Phase 6 TSC072F4 BAYHTRS409 9 0 1 18 2 25 19 3 25 6 TSC072F4 BAYHTRS418 18 0 1 3...

Page 14: ...drive standard efficiency Unit Model Amps Tons Number No Volts Phase hp FLA LRA 6 T YSC072F3 1 208 230 3 2 00 6 30 48 0 6 T YSC072F4 1 460 3 2 00 3 6 24 0 6 T YSC072FW 1 575 3 2 00 2 50 18 2 Table 18...

Page 15: ...raturetowithin 2 Fofthesensor setpoint at the sensed location Three Stages of Cooling1 When the unit is configured for three stage cooling and the system switch is set to the cool position and the zon...

Page 16: ...ling or heating from the space temperature controller i e zone sensor or thermostat while in reheat the reheat valve is de energized and the compressor continues to run or the heat is turned on The 3...

Page 17: ...1 AmbientTemperature controlling the economizing cycle by sensing the outside air dry bulb temperature Table 20 p 17 lists the selectable dry bulb values by potentiometer setting 2 Reference Enthalpy...

Page 18: ...ne sensor or Building Automation System BAS will be required Cycling unit power will also clear the fault Electromechanical Controls These units are offered with two control options electromechanical...

Page 19: ...first stage electric heat contactor AH or AH CH is energized If the first stage of electric heat can not satisfy the heating requirement the thermostat closes W2 When theW2 contacts close the second s...

Page 20: ...odule diagnostics Steady light Module is powered up but no active call for heat Blinking at continuous steady rate Active call for heat One blink Loss of communication Two blinks System lockout failur...

Page 21: ...indoor coil 3 Measure the outdoor air dry bulb temperature 4 Take discharge and suction pressure readings 5 Plot the outdoor dry bulb and the indoor DB WB temperature onto the chart 6 At the point of...

Page 22: ...22 RT SVF25C EN Subcooling Charging Chart Figure 2 T YSC072F subcooling charging chart...

Page 23: ...ircuit Figure 3 Refrigerant circuit diagram Compressor Filter Drier Air Air TXV Refrigerant Flow Cooling System 1 Service Valve High Pressure Control DLTS Low Pressure Control Service Valve Service Va...