Replacement Procedure

6

 PART-SVN114A-EN

16. Remove the collector plate cover and gasket behind it. 

If the gasket behind the part is damaged, replace with 
the new gasket provided in the kit.

17. Remove the cover plate on the indoor fan motor.

18. Loosen the strain relief on the indoor fan motor.

19. Disconnect motor wiring and remove wiring from 

motor housing.

20. Loosen the locking nut on the indoor blower motor 

mount (see 

Figure 4, p. 6

).

21. Rotate the acorn nut counterclockwise. This will loosen 

the fan belt.

22. Remove the belt.

23. Remove the indoor blower motor assembly.

24. Remove the motor mounting plate and the side wall 

cover. 

Note:

The side wall cover will have to pivot from the 
top because copper tubing will be routed from 
the condensing section to the evaporator.

25. Push the heat exchanger out from the rear supply duct 

through the front of the unit. Use two people when 
doing this so that the unit is not damaged.

26. Remove the three screws on each side of the fan 

housing.

27. Lift the rear side of the fan housing (closest to the 

outdoor divider panel) and install the service air baffle 
by sliding the clips in the baffle over the edge of the 
heat wrapper flange (see 

Figure 5

).

28. Lower the fan housing and secure it to the heat 

wrapper with the screws removed in 

Step 26

 (three 

screws per side).

29. Remove the heat exchanger support rod by removing 

the tinnerman clip on the coil side of the heat wrapper 
and the screw on the outer side of the divider panel.

30. Use a 5/16 in. drill bit and create a new hole in the heat 

wrapper and outdoor divider panel that is 6.0 in. in 
front of the old heat exchanger support rod holes 
(

Figure 5

). Use the same height for each new hole 

location as the old location.

31. Re-install the 1/4 in. heat exchanger support rod in the 

new hole location. On the outdoor divider panel side 
that has the bent tab on the rod, use a 1/8 in. drill to 

Figure 3.

Figure 4.

Figure 5.

Lift the fan 
housing to 
install the 
service air 
baffle over the 
rear flange.

New support 
rod hole 
location for 
shorter heat 
exchanger.

6 in

.

Heat Wrapper

Summary of Contents for Trane YSC072E M Series

Page 1: ...red equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to the equipment Heat Exchanger Replacement For a Shorter Heat Exchanger Replacement Installation Instructions PART SVN114A EN December 2015 Models Y C072A L X YSC072E M Y YSC 090 092 A L X YSC07...

Page 2: ...ndicates a potentially hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or property damage only accidents WARNING Proper Field Wiring and Grounding Required Failure to follow code could result in death or serious injury All field wiring MUST be perfor...

Page 3: ...ks All trademarks referenced in this document are the trademarks of their respective owners Revision History PART SVN114A EN 15 Dec 2015 First version of this literature WARNING Hazardous Voltage and Gas Failure to turn off gas or disconnect power before servicing could result in an explosion or electrocution which could result in death or serious injury Turn off the gas supply and disconnect all ...

Page 4: ...ecific components and other options for any specific unit When ordering replacement parts or requesting service be sure to refer to the specific model number and serial number printed on the unit nameplate Tools Required 5 16 in Driver 5 16 in Long Driver 12 15 in 5 16 in Ratchet 9 16 in Wrench 1 2 in Socket Ratchet Extension Tube of RTV Max temperature rating of 500 F field supplied Screw used to...

Page 5: ...gure 2 If the gasket behind the part is damaged replace with the new gasket provided in the kit 14 Remove the air orifice Please note that when installing the new heat exchanger this air orifice plate may need to be changed out depending on the unit refer to Table 1 p 7 15 Remove the screws shown in Figure 3 to take out the collector cover Note that these screws are longer than the other screws in...

Page 6: ...move the three screws on each side of the fan housing 27 Lift the rear side of the fan housing closest to the outdoor divider panel and install the service air baffle by sliding the clips in the baffle over the edge of the heat wrapper flange see Figure 5 28 Lower the fan housing and secure it to the heat wrapper with the screws removed in Step 26 three screws per side 29 Remove the heat exchanger...

Page 7: ...it install the turbulators provided in the kit 34 Reassemble the unit Retrace Step 24 through Step 1 35 Verify the alignment of the indoor blower fan belt Table 1 Parts to install in the replacement heat exchanger Model Number Size of Old Heat Exchanger Size of New Heat Exchanger Turbulators Installed in Replacement New TCO1 Limit Installed in Replacement New Air Orifice Installed in Replacement Y...

Page 8: ...olio of advanced controls and HVAC systems comprehensive building services and parts For more information visit www Trane com Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice We are committed to using environmentally conscious print practices that reduce waste 2015 Trane All rights reserved PART SVN114A ...

Reviews: