6
RT-SVF28F-EN
Evaporator Fan Performance
Table 2.
Direct drive evaporator fan performance - 10 tons standard efficiency - TSC120F3,4,W downflow airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
cfm
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm
bhp
rpm
bhp
3200 1028 0.67 1054 0.74 1079 0.81 1105 0.88 1131 0.96 1157 1.04 1184 1.12 1209 1.21 1234
1.30
1258
1.38
3600 1150 0.93 1173 1.01 1196 1.09 1219 1.17 1242 1.25 1265 1.34 1288 1.43 1312 1.52 1335
1.61
1357
1.71
4000 1272 1.25 1294 1.34 1315 1.43 1335 1.52 1356 1.61 1376 1.70 1397 1.80 1418 1.90 1440
2.00
1460
2.09
4400 1395 1.65 1415 1.75 1435 1.84 1453 1.94 1472 2.04 1490 2.14 1509 2.24 1528 2.34 1547
2.45
1566
2.56
4800 1518 2.12 1537 2.23 1555 2.33 1572 2.44 1590 2.54 1606 2.65 1623 2.76 1641 2.87 1657
2.98
1675
3.10
continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm
bhp
rpm
bhp
3200 1280 1.46 1302 1.54 1324 1.63 1347 1.71 1370 1.80 1392 1.89 1414 1.99 1436 2.09 1458
2.19
1479
2.28
3600 1379 1.80 1401 1.90 1422 2.00 1441 2.09 1461 2.18 1480 2.27 1501 2.36 1521 2.46 1542
2.57
1561
2.67
4000 1481 2.20 1501 2.30 1522 2.41 1542 2.52 1561 2.63 1579 2.73 1597 2.84 1614 2.94 1631
3.04
1649
3.14
4400 1585 2.67 1604 2.78 1623 2.89 1642 3.01 1660 3.12 1679 3.25 1696 3.36
—
—
—
—
—
—
4800 1693 3.22
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Notes:
1. For Direct Drive Evaporator Fan Speed (rpm), reference
.
2. Data includes pressure drop due to standard filters and wet coils.
3. Refer to
to determine additional static pressure drop due to other options/accessories.
4. Direct Drive Fan Motor Heat (MBH) = 2.8623xFan BHP -0.1504
5. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously
at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or
premature motor failure. Our product's warranty will not be affected.
Table 3.
Direct drive evaporator fan performance - 10 tons standard efficiency - TSC120F3,4,W horizontal airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
cfm
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm
bhp
rpm
bhp
3200 1016 0.65 1044 0.72 1070 0.79 1097 0.87 1123 0.95 1148 1.03 1173 1.10 1197 1.18 1221
1.26
1245
1.34
3600 1137 0.91 1162 0.99 1185 1.07 1209 1.15 1232 1.24 1256 1.32 1279 1.41 1301 1.49 1323
1.58
1344
1.66
4000 1258 1.22 1280 1.31 1302 1.40 1323 1.49 1344 1.58 1366 1.68 1387 1.78 1408 1.87 1428
1.97
1448
2.06
4400 1379 1.60 1400 1.70 1420 1.80 1439 1.90 1459 2.00 1478 2.10 1497 2.21 1517 2.32 1535
2.42
1554
2.52
4800 1501 2.06 1520 2.17 1538 2.28 1557 2.38 1575 2.49 1592 2.60 1609 2.71 1627 2.83 1646
2.94
1663
3.06
continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm
bhp
rpm
bhp
3200 1269 1.43 1293 1.52 1317 1.61 1339 1.70 1361 1.78 1383 1.87 1404 1.96 1425 2.05 1447
2.14
1468
2.24
3600 1366 1.75 1386 1.84 1408 1.94 1429 2.04 1451 2.15 1472 2.25 1492 2.35 1513 2.45 1532
2.54
1551
003
4000 1467 2.15 1487 2.25 1506 2.34 1525 2.44 1544 2.55 1563 2.65 1582 2.76 1602 2.89 1620
3.00
1639
3.12
4400 1573 2.63 1591 2.73 1609 2.84 1626 2.94 1643 3.04 1661 3.15 1679 3.26 1696 3.37
—
—
—
—
4800 1681 3.18 1698 3.29
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Notes:
1. For Direct Drive Evaporator Fan Speed (rpm), reference
.
2. Data includes pressure drop due to standard filters and wet coils.
3. Refer to
to determine additional static pressure drop due to other options/accessories.
4. Direct Drive Fan Motor Heat (MBH) = 2.8623xFan BHP -0.1504
5. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously
at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or
premature motor failure. Our product's warranty will not be affected.