INFOSEC UPS SYSTEM
–
4 rue de la Rigotière
–
44700 Orvault
–
France
–
www.infosec-ups.com
Hot Line Tel : +33 (0)2 40 76 15 82
–
fax : +33(0)2 40 94 29 51
–
–
03 16 AA 59 203 26
3-6. LCD Setting
There are three parameters to set up the UPS. Refer to the following diagram.
Parameter 1 is for program alternatives. There
are 20 programs to set up. Refer to the table
below.
Parameter 2 and parameter 3 are the setting
options or values for each program.
NOTE:
Select “Up3 or “Down” buttons to
change the programs or parameters.
List of 20 programs available for parameter 1:
Code Description
Bypass
AC
CVCF Battery Battery Test
01
Output voltage
Y
02
Output frequency
Y
03
Voltage range for bypass
Y
04
Frequency range for bypass
Y
05
Reserved
06
Reserved
07
Reserved
08
Bypass mode setting
Y
Y
09
Battery maximum discharge time setting
Y
Y
Y
Y
Y
10
Reserved
11
Reserved
12
Reserved
13
Battery voltage Calibration
Y
Y
Y
Y
Y
14
Reserved
15
Inverter voltage Calibration
Y
Y
Y
16
Floating charger voltage adjustment
Y
Y
Y
Y
Y
17
Constant charger voltage adjustment
Y
Y
Y
Y
Y
18
Charger maximum current setting
Y
Y
Y
Y
Y
19
Battery capacity and groups setting
Y
Y
Y
Y
Y
20
Backup time calibration
Y
Y
Y
Y
Y
*Y (YES) means that this program can be set in this mode.
01: Output voltage
Interface
Setting
Parameter 3: Output voltage
You may choose the following voltage in parameter 3:
208:
output voltage is 208VAC
220:
output voltage is 220VAC
230:
output voltage is 230VAC
240:
output voltage is 240VAC
Parameter 1
Parameter 2
Parameter 3