2 battery packs can be joined to constitute a rack system
3000VA
Install the 3000VA series into the 19” rack as shown below.
.
1. Turn on the UPS and connect the load.
2. After installing the UPS in rack, the load may be connected. Make sure the load
equipment is turned off, and then plug all loads into the output receptacle properly
protected by a circuit breaker fuse in accordance with national and local electrical
codes.
11. Emergency Power Off (EPO) set up
The 1500/2000VA and 3000VA include EPO port that allows an immediate power shut
down in the protected equipment and does not follow the shutdown procedure from any
power management software.
Note: When the EPO switch is reset, the equipment will not return to battery power until the
UPS is manually restarted. If the power switch to turn off the UPS after EPO is pressed, the
UPS remains in Standby mode until pressing the power switch to turn on the UPS again.
Follow the procedure below to install the EPO switch.
1. Check the UPS is turned off.
2. Remove the EPO connector from the EPO port on the rear panel of the UPS