INFOSEC UPS SYSTEM
– 15, Rue du Moulin – 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line
– Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - [email protected] – 11 17 AA 59 204 17
26
6 . T E C H N I C A L S P E C I F I C A T I O N
E3 PRO
1000 RT
E3 PRO
2000 RT
E3 PRO
3000 RT
Technology
On Line Double Conversion
Capacity
1000 VA/900W
2000 VA/1800W
3000 VA/2700W
Power Factor
0,9
PHYSICAL CHARACTERISTICS
Dimensions L x l x h (mm)
– UPS (2U)
310 x 438 x 88
410 x 438 x 88
630 x 438 x 88
Net Weight (kg) - UPS
12.7
19
29,3
INPUT
Voltage
110/115/120/127VAC or 208/220/230/240 VAC*
Input nominal voltage
60-145 VAC or 120-300 VAC at 50% load
90-145 VAC or 180-300 VAC at 100% load
Frequency Range
40-70 Hz
OUTPUT
Voltage
110/115/120/127VAC or 208/220/230/240 VAC*
Voltage Regulation
± 1%
Frequency Range (Synchronized Range)
47~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode)
50 Hz ± 0.25 Hz or 60 Hz ± 0.23 Hz
Current Crest ratio
03:01
Harmonic distorsion
≦
3 % THD (Linear Load)
≦
6 % THD (Non-linear Load)
Transfer Time
Line mode to Battery
mode
0ms
Inverter to Bypass
0ms
Waveform
Pure Sinewave
IEC outlets standards
3 (10A)
4 (10A)
4 (10A)+terminal
EFFICIENCY
AC mode
88%
89%
90%
Battery mode
83%
87%
88%
Eco mode
93%
94%
95%
BATTERY
Battery charger
Operates when UPS connected to mains
Charging current
Adjustable from 1 to 3.5A
Battery type
12 V9 AH
12V9Ah
12V9Ah
Batt specs & Number
2
4
6
Typical Recharge Time
4 hours recover to 90% capacity
Charging voltage
27.4VDC ± 1%
54.7 VDC ±1%
82.1 VDC ±1%
Backup time
From 5 to 30 min. depending on the connected load
INDICATORS
LCD display
Load level, Battery level, AC mode, Battery mode, Bypass mode,
and Fault indicators
ALARMS
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously sounding
MANAGEMENT / COMMUNICATION
Communication
USB Port and RS232 & Infopower software included (support
Windows family, Linux, Unix et MAC)