19
Temperature - Battery lifetime
0,001
0,01
0,1
1
10
100
0
10
20
30
40
50
60
70
80
Temperature [
o
C]
Battery Lifetime [year]
To check the autonomy time for certain load level, you choose normal operating mode, please turn the
input fuse to “0” position while the UPS is loaded with the desired load level. Then UPS passes to battery
mode. You will see on the screen BUV sign, UPS will shutdown in a few minutes. The time between by-
pass mode and switch off of the UPS is the autonomy time. If you don’t want any interruption on the
load, please turn the input fuse to “I” position when you see the BUV message.
Please make sure that the batteries are full before the test.
5.1.3.4
Temperature Management
UPS measures the temperature of some points inside the UPS, and calculates the temperature of
semiconductor junctions by using electrical values, temperature of which is immeasurable. In this way;
Overload time is precisely calculated.
UPS is able to perform advanced over-temperature protection.
5.1.3.5
Communication Interface
Please contact to authorized distributor to be informed how to get SNMP adapter, software,
communication cable, modem …etc.
Communication interface has the following features;
Communication without operator,
Direct communication between your PC and UPS,
Add as a new Client to the Network,
Inform the operating mode to an external unit.
Above features are optional.
Do not remove or plug in communication interface during bad weather (such as lightning)
conditions.
5.1.3.5.1
Free Contact Communication
UPS 9-Pins D-SUB female socket (free contact) gives the following signals;
UPS shutdown
This feature is used for remote shutdown and switch on via PC.
(Pin 6: high (+ 5V... + 12V), Pin 7: 0V)