7. OPERATING PROCEDURES
7.1. Preparations
UPS is shipped with 3pcs battery fast fuses in a plastic package attached to the rear side
of UPS. Separate
the package from UPS and take out the fuses.
After all connections are completed as described in
, the battery fuses must be placed as shown
below.
Do not leave the battery fuse package at the front of UPS. Otherwise the fans would be
blocked and UPS may overheat.
Do not close battery fuse holder F5 before reading Commissioning procedure
Mount the battery fast fuses into battery fuse holder on the UPS. Fast fuses indicators side
must be placed upper side of the holder.