INFLUX MEASUREMENTS SprinklerSense FTI Manual To The Installation, Operation & Maintenance Download Page 6

IOM FTI Iss.1 

October 2018 

Page 6 of 8 

 

2.2 

Electrical & Power Supply 

THIS IS AN EXTRA-LOW VOLTAGE DEVICE, DO NOT CONNECT TO MAINS VOLTAGES OR 

CONNECT MAINS VOLTAGES WITHIN THE BOX. 

 

 

Power Supply and Battery 

The SprinklerSense system requires a D.C. power supply connection within the range of 9 to 30 Volts.  This 
allows it to be supplied using proprietary battery backup systems of either 12 or 24V DC. The average power 
consumption of the system including the SPDB30/90 and the FTI is circa 1.2Watts. 

To provide battery backup to supply both the Flow switch and the FTI for a 72 hour period, use the following 
capacity batteries: 

For 12V systems, 7 Ah 

For 24V systems, 5 Ah 

The power supply connections should be connected to the FTI at J1 terminals 2 and 3, (12-24V and 0V). 
J1 Terminal 1, Earth terminal should be connected to electrical earth. 

FTI to Flow Switch 

A 4-core cable should be used to connect the FTI directly to the flow switch unit, using J1 terminals 4 to 7 in the 
FTI to terminals 1 to 4 in the flow switch. Connect V+ to V+, V- to V-, COMS+ to COMS+ and COMS- to 
COMS-. Shown in wiring diagram below. 

Relay Outputs 

Connect the SPDB30/90 flow switch outputs as required, referring to the SPDB30/90 instructions. 

The switch outputs from the FTI can also be connected if required. The Flow output switch consists of a 
common connection (COM), a Normally Open contact (NO) and a Normally Closed contact (NC).  The contacts 
are in their Normal state during non-flow conditions. The output switches should be connected as required, in the 
same way as traditional flow switch micro-switch outputs.  The contact ratings of 24VDC and 500mA should not 
be exceeded. 

The ERROR output provides a relay contact switch which can be used to warn of possible failure of the flow 
switch or of poor sprinkler pipe conditions which may adversely affect the function of the sprinkler system. 
There is one ERROR output switch consisting of a Common connection (COM), a Normally Open contact (NO) 
and a Normally Closed contact (NC). The contacts are in their normal state during the non-error condition.

 

 

 

 

Summary of Contents for SprinklerSense FTI

Page 1: ...O THE INSTALLATION OPERATION MAINTENANCE OF SprinklerSense Fixed Test Interface Unit FTI FOR USE WITH SPDB30 SPDB90 TYPE FLOW SWITCHES Contents Page 1 Specification Operation 2 1 1 Introduction 2 1 2...

Page 2: ...mA 1 3 Operation The FTI is connected to the SprinklerSense flow switch via a serial communications link wired It continuously requests status information from the sensor and reacts accordingly In nor...

Page 3: ...the unit will timeout back to its normal ON mode To start a test if the key has been left in the TEST position and timed out the key must be returned to ON position and then re set to TEST Flow Switch...

Page 4: ...tallation refer to the software installation guide If the software is installed but USB OK is not displayed when expected it is likely that the PC has not yet recognised that the device is connected T...

Page 5: ...ed with a minimum depth of 35mm The box should be mounted in an easily accessible position where it is not likely to become wet in normal use Cable entries should be made available for cables 1 from t...

Page 6: ...itch unit using J1 terminals 4 to 7 in the FTI to terminals 1 to 4 in the flow switch Connect V to V V to V COMS to COMS and COMS to COMS Shown in wiring diagram below Relay Outputs Connect the SPDB30...

Page 7: ...on a separate block J5 for remote key switch actuation These terminals must only be connected to volt free contacts such as a mechanical switch or relay contacts Connection to other types of circuit...

Page 8: ...that the power supply is correct and turned on If the Remote Key Switch input is connected disconnect and try unit again If the unit still does not function it should be replaced by a new unit FTI uni...

Reviews: