2.2 

Electrical & Power Supply 

 

 
Before installing the unit the flow signal delay timer can be set.  Remove the top lid and locate the rotary 
position switch mounted on the PCB.  Setting ‘0’ will select the minimum delay and setting ‘9’ the maximum 
delay.  Settings between these will set the delay proportionally. The factory set default position is 9. 
 
Two 20mm holes are provided for cable entry.  These should be fitted with appropriate cable glands or conduit 
depending upon site requirements. There is no requirement to seal the conduit entry holes if conduit is used. 
 
The SprinklerSense unit requires a D.C. power supply connection.  This allows it to be supplied using 
proprietary battery backup systems of 24V DC. The average power consumption of the unit is circa 1Watt. 
 
The Amp Hour (Ah) rating of the batteries required can be calculated using an average current draw of 60mA on 
a 24V system.  This mA figure should be multiplied by the number of hours that the batteries are required to last. 
 
For example, if a 24V backup battery is required to last for 72 hours, 0.06A x 72h = 4.32 Ah. 
There-fore a 24V battery supply with a rating of at least 5Ah should be used. 
The power supply connections should be connected to the V+ and V- terminals.  The Earth terminal should also 
be connected to electrical earth. 
 
There are two flow output switches.  These both activate at the same time but are electrically isolated from each 
other.  Each output switch consists of a common connection (COM1 or COM2), a Normally Open contact (NO1 
or NO2) and a Normally Closed contact (NC1 or NC2).  The contacts are in their Normal state during non-flow 
conditions.  The output switches should be connected as required, in the same way as traditional flow switch 
micro-switch outputs.  The contact ratings of 24V D.C. and 500mA should not be exceeded. 
 
D

O NOT CONNECT THE REMAINING TERMINALS WITHOUT REFERRING TO THE SEPARATE LEAFLET WHICH IS 

AVAILABLE FOR FURTHER INFORMATION ABOUT THE AUXILIARY CONNECTIONS

 

 

Summary of Contents for SPDB 30

Page 1: ...ITCHES IN AUTOMATIC SPRINKLER INSTALLATIONS Contents Page 1 Specification Principle of Operation 2 1 1 Introduction 2 1 2 Construction Specification 2 1 3 Principle of Operation 2 2 Installation 3 2 1 Mechanical 3 2 2 Electrical Power Supply 5 3 Operation 6 3 1 Flow 6 3 2 Auxiliary Relay Output 6 4 Maintenance 6 4 1 Normal 6 4 2 Fault 6 TYPE FIREGROOVE TYPE FIREFLANGE M e a s u r e m e n t s L t d...

Page 2: ...ure Range 2 to 68 C Input Voltage 24V D C Flow Switch Output 1x DPCO Relay 30V D C 2A Adjustable Delay Type SPDB 30 0 to 30 seconds Type SPDB 90 0 to 90 seconds Flow rate Sensitivity The switch will operate at all flow rates above 60 L min The switch will not operate at flow rates less than 10 L min 1 3 Principle of Operation Water flow passing the sensor probe causes a change in relative temperat...

Page 3: ...possibility of positioning the probe where a permanent air pocket is likely to occur Table 2 1 b shows mechanical Tees and adaptors that can be used when replacing a mechanical flow switch in an existing installation After applying suitable thread sealant or PTFE tape to the threads the unit should be hand tightened into the Mechanical Tee and then finally tightened using a spanner to form a press...

Page 4: ...IOM SPDB Iss 2 ENG March 2019 Page 4 of 6 2 1 b Top and side mounting positions on horizontal pipe ...

Page 5: ...raw of 60mA on a 24V system This mA figure should be multiplied by the number of hours that the batteries are required to last For example if a 24V backup battery is required to last for 72 hours 0 06A x 72h 4 32 Ah There fore a 24V battery supply with a rating of at least 5Ah should be used The power supply connections should be connected to the V and V terminals The Earth terminal should also be...

Page 6: ...her auxiliary relay is provided in the unit which can be used for other supervisory duties outside of the scope of EN 12259 5 A separate leaflet is available for further information on additional functions 4 Maintenance 4 1 Normal The SprinklerSense flow switch uses solid state sensing technology and requires no routine maintenance in normal operating conditions Ensure any valves controlling the w...

Reviews: