1. This product is intended for use only on data circuits with operating 

voltages not to exceed 12VDC and DC power circuits with operating 

voltages not to exceed 60VDC and operating currents not to exceed 

10A.

2. Mounting the ALPU-TSU (See Diagram):  Mount the device as close 

to the equipment to be protected as possible using the provided hard-

ware and the concealed mounting holes.  Mount the unit in the orienta-

tion shown, with the strain reliefs facing the ground.

3. Wiring the ALPU-TSU

     3.1 The ALPU-TSU surge suppressor is bidirectional and may  

     be wired in either orientation. 

     3.2 Removing the Cover: Remove the 4 cover screws using a  

     Phillips screwdriver and lift off the cover.

     3.3 Wiring: Thread a multiconductor cable from the data source  

     through one of the strain reliefs on the bottom of the unit.  Strip back  

     the cable jacket as needed, then strip 1/4” off of each conductor.   

     Gently pull the terminal block off of the pcb pins, then install each  

     conductor into the corresponding screw-down location using the  

     callouts on the pcb and the color legend on the inside of the lid as a  

     guide.  Finally, install the terminal block onto the pin strip by firmly  

     pressing it into place and tighten the strain relief onto the cable (Do  

     not over torque!!).  Repeat this procedure for the outgoing multicon 

     ductor cable running to the equipment to be protected. Reinstall the  

     cover.

     3.4 Grounding: Connect the external ground lug on the enclosure to  

     a solid Earth ground. The unit must be grounded for the suppressor  

     to operate properly!

800.882.9110  |  208.772.8515  |  www.transtector.com

ALPU-TSU

1200-153 REV E