Infinite Transtector ACINV Series Installation Manual Download Page 7

Installation Manual

 | ACINV Series 1RU Rack Mount Inverters

12

13

 +1 (208) 635-6400  |  www.transtector.com

 +1 (208) 635-6400  |  www.transtector.com

   

2.4.4  Before proceeding further, carefully check that the cables you have just connected to the negative terminal 

of inverter are connected to the negative DC power source.

    

 

 

CAUTION!

   

 

 

 

Reverse polarity connection will blow a fuse in inverter and may

   

 

 

 

permanently damage the inverter.

   

 

 

 

Damage caused by reversing polarity connection is not covered

   

 

 

 

by our warranty.

   

2.4.5  Set the power switch to the ON position.  After a moment you will hear three beeps.  At the same time, 

the display scrolls the word “TRANSTECTOR” twice.  After that, you will hear a continuous sound from 

internal alarm.  When the AC output voltage shows on the display the unit will have completed the start-up 

sequence.

 

   

2.4.6  Set the power switch to the OFF position.  The unit should shut down completely. 

   

2.4.7  To accurately measure the true output R.M.S. voltage of inverter connect to one of the outlet sockets and 

then set the power switch to ON.  Voltage will appear at the output sockets after the start-up sequence is 

completed.

  2.5 Safety Grounding

During the AC wiring installation, AC input and output ground wires are connected to the inverter.  The AC input ground 

wire must be connected to the incoming ground from your AC utility source.

The AC output ground wire should go to the grounding point for your loads (for example, a distribution panel of bus 

chassis).

   

2.5.1  Neutral Grounding - 120V models only. 

   

 

The neutral conductor of the AC output circuit of the Inverter is connected to the safety ground during 

inverter operation.  This conforms to national electrical code requirements that separately derived AC 

sources (such as inverters and generators) which have their neutral conductors tied to ground in the same 

way that the neutral conductor from the utility is tied to ground at the GFCI breaker panel.  When AC utility 

power is connected and the inverter is in bypass mode, this connection (neutral of the Inverter’s AC output 

to input safety ground) is not present so that the utility neutral is only connected to ground at your breaker 

panel, as required.

  2.6 Making DC Connections

 

Follow this procedure to connect the battery cables or those from another DC source to the DC input terminals on the 

Inverter. Your cables should be as short as possible (ideally, less than 10 feet / 3 meters) and large enough to handle the 

required Current in accordance with the electrical codes or regulations applicable to your installation. 

Cables that are not an adequate gauge (too narrow) or are too long will cause decreased inverter performance such as 

poor surge capability and frequent low input voltage warnings and shutdowns. 

These low input voltage warnings are due to DC voltage drop across the cables from the inverter to the batteries / other 

DC source.

The longer and narrower these cables, the greater the voltage drop.

 

 

   

WARNING!

  

 

 

 

The installation of a fuse must be on the positive cable.

  

 

 

 

Failure to place a fuse on [+] cables running between the

  

 

 

 

inverter and battery or other DC source may cause damage

  

 

 

 

to the inverter and will void the warranty.

 

  

 

 

 

Connections must not be made when the DC source is live.

Increasing your DC cable size will help to improve the situation.

TRANSTECTOR recommends the following cables for optimum inverter performance.

Model NUMBER

1kVA models

Wire

Size

 1

In-line

Fuse

Model NUMBER

2kVA models

Wire

Size

 1

In-line

Fuse

ACINV1-1KVA

#6AWG

40A

ACINV2-2KVA

#2AWG

70A

Notes:

1.  Use only high quality copper wiring and keep cable length from 3-6 feet (~1-2m).

2.  The maximum wire size that the black and red input connectors can accept directly is #2AWG.  

These models are supplied with two types of adaptor for use in different applications. One type 

MUST be fitted into the connectors to allow for the greater wire size required.

A suitable breaker, at the DC source, for isolation and overload protection is recommend.

  2.7  Alarm Connection

 It is important to note that the electronic circuits associated with this function are directly connected within the 

AC output circuits of the inverter and that for this reason the relay contact connections that are provided on the 

rear panel mounted wire clamp connector MUST be considered to be at a non-SELV potential and all necessary 

precautions to protect the operator from electric shock hazard must be taken.

These relay contacts must not be connected directly to any SELV or other safety connected circuit and any 

cables or wiring used for such connections must be double insulated.

  2.8  Inverter Operation

To operate the power inverter, turn it on using the ON/OFF switch on the front panel.  The power inverter is now 

ready to deliver AC power to your loads. 

If you are operating several loads from the power inverter, turn them on separately after the inverter has been 

turned on.  This will ensure that the power inverter does not have to deliver the starting currents for all the loads 

at once.

 

 

   

CAUTION!

  

 

 

 

EXTERNAL SURFACES GET HOT.

  

 

 

 

During the period of the unit running, the case may become very

  

 

 

 

warm. Please do not touch the side marked. “

” directly. 

  

Summary of Contents for Transtector ACINV Series

Page 1: ...Installation Manual 2020 Infinite Electronics Inc Transtector is a registered trademark of Infinite Electronics Inc ACINV M Rev 1 ACINV Series 1RU Rack Mount Inverters...

Page 2: ...with Batteries 16 6 DIP switch settings 17 7 Communications Protocol Remote ON OFF Function 17 REV DESCRIPTION CHK d APPR d DATE 1 Initial Release DWR 09 15 20 Product Support Product support can be...

Page 3: ...for 1 minute 2040W for 20 seconds Efficiency FL 89 90 Output Voltage 100 110 115 120VAC 3 switch selectable Output Frequency 50Hz or 60Hz 0 05 switch selectable Peak Output Current 15A Output Waveform...

Page 4: ...ON OFF Switch Switches the inverter electronics ON and OFF Should be in the OFF position during installation 2 1 2 Function Selector LEDs Display When the function selector is sequentially pushed the...

Page 5: ...inal of the battery or DC source must be connected to the negative terminal of the battery or DC source WARNING Reverse polarity connection will blow an internal fuse and may also damage the unit beyo...

Page 6: ...tion between the earthed conductor of the same DC supply circuit and the earthing conductor and also the point of earthing of the DC system The DC system shall not be earthed elsewhere 2 3 12 The DC s...

Page 7: ...nce with the electrical codes or regulations applicable to your installation Cables that are not an adequate gauge too narrow or are too long will cause decreased inverter performance such as poor sur...

Page 8: ...ecause it has been operated at power levels above its rating or because it has been installed in a location which does not allow it to dissipate heat properly The unit will automatically restart once...

Page 9: ...tall in compartments containing batteries or flammable materials or in locations where require ignition protected equipment This includes any space containing gasoline powered machinery fuel tanks or...

Page 10: ...V SPEC AC I P fault voltage is 140 0V SPEC AC O P voltage is 208 4V AC O P current is 34 AC O P frequency is 59 9 HZ DC I P voltage is 54 2V Temperature is 35 0 degrees centigrade RS232 Hardware conne...

Reviews: