Inferno SFI-6000 Installation Instructions Download Page 1

Fig. 1   Sight Feed Indicator (SFI) Assembly

Thank  you  for  choosing  "INFERNO"  products.  Inferno
products are designed and constructed to give satisfactory
performance in a wide range of environmental and operat-
ing  conditions.    If  the  correct  design  and  materials  were
specified at the time of purchase, satisfactory service will
depend  on  reasonable  care  in  the  subsequent  installation,
operation, and maintenance of the product.

INSTALLATION

To  help  ensure  trouble-free  operation  of  your  sight  feed
indicator (SFI), read this Instruction Manual carefully and
follow its recommendations.  Failure to follow any instruc-
tion could possibly result in a malfunction of the gage or
glass  breakage  during  service,  which  can  cause  property
damage or bodily injury.

Before  installing  the  gage  the  following  items  should  be
considered:

•    Check  for  suitability  of  the  SFI  in  service  before
installing. 
•  Check chemical compatibility of process with materials
of SFI construction. 
•    Check  maximum  pressure  and  temperature  of  service
with ratings of the SFI (see Fig. 1).  Do not exceed ratings
of the SFI in service.

Fig 2- SFI Pressure & Temperature Rating

OPERATION

A.  Hydrostatic Test

We recommend a hydrostatic test on the gage assembly at
1.5 times the operating pressure whenever possible, espe-
cially in high pressure applications. The SFI is factory test-
ed to 1.5 times the rated pressure and does not need to be
re-tested  at  time  of  installation.  However,  if  glasses  and
seals have been replaced during maintenance, then the SFI
should be re-tested by the user.

CAUTION:

DO  NOT  USE  WRENCH  ON  GLAND

NUTS.  If a leak develops during testing, do not use wrench
to tighten gland nuts.  Wait until the pressure has been vent-
ed to atmosphere before attempting any work on the SFI.
Hand-tight the gland nuts.  If it does not eliminate the leak,
disassemble the SFI and follow the maintenance procedure.

B.  Starting Up

If a large temperature difference exists between the SFI and
process  fluid,  raise  or  lower  the  temperature  slowly  by
cracking  the  connecting  valves  open.    Do  not  open  the
valves all the way until the SFI is either fully warmed up or
cooled down. The glass used in the SFI is tempered borosil-
icate glass that can stand large temperature shocks.  But the
amount is limited by other factors such as stresses imposed
during  installation  which  reduces  the  glass  resistance  to
thermal shock.

INFERNO

Installation Instruction: M991012 Rev B

Rev. Date:10-30-12

Replaces: 9-06

I

NSTALLATION

/ O

PERATION

/ M

AINTENANCE

I

NSTRUCTION

6000# SIGHT FEED INDICATOR

GLAND NUT

Nozzle

Glass

M

ODEL

SFI-6000