background image

 

 
PRO1 series   

DIN rail single phase two wire energy meter

 

 

 

 
 
 

PRO1D V11.112 
PRO1D V11.121 
PRO1D V11.122 
PRO1D V11.211 
PRO1D V11.212 
PRO1D V11.221 
PRO1D V11.222 
PRO1TE V11.311 
PRO1TE V11.312 
PRO1TE V11.321 
PRO1TE V11.322

 

 

 
 
Version 1.0 

 
 
 
 
 
 
 
 
 
 
 
 
 
Note: the picture on the frontpage is a meter from the series of this meter, it might not 
be exactly the same as the meter you have bought 

Summary of Contents for PRO1 Series

Page 1: ...121 PRO1D V11 122 PRO1D V11 211 PRO1D V11 212 PRO1D V11 221 PRO1D V11 222 PRO1TE V11 311 PRO1TE V11 312 PRO1TE V11 321 PRO1TE V11 322 Version 1 0 Note the picture on the frontpage is a meter from the series of this meter it might not be exactly the same as the meter you have bought ...

Page 2: ... 5 Performance criteria 6 6 Specifications 6 7 Basic errors 7 8 Description 7 9 Dimensions 8 10 Torque tables 8 11 Installation 8 12 Operation 9 12 1 Consumption indication 9 12 2 Reading the meter 9 12 3 Mechanical register 9 12 4 Digital register 10 12 5 Pulse output 10 13 Troubleshooting 11 14 Technical support 12 15 SOP Table 12 ...

Page 3: ...commended and approved by Inepro Metering B V Proper handling The prerequisites for perfect reliable operation of the product are proper transport storage installation and connection as well as proper operation and maintenance During its operation certain parts of the meter might carry dangerous voltages Only use insulated tools suitable for the voltages this meter is used for Do not connect while...

Page 4: ...nepro has a wide product range of devices We have introduced a large number of energy meters on the market suitable for 110V AC to 400V AC 50 or 60Hz Besides the normal energy meters we also developed our own pre paid meters with chip card chip card re loaders and a complete PC management control system For more information on other products please contact our sales department at sales ineprometer...

Page 5: ... 2011 5 For the SOP number see section 15 PRO1 V11 xxx 4 MID certificate ...

Page 6: ... PRO1TE series Nominal voltage Un 230V AC Operational voltage 195 253V AC Insulation capabilities AC voltage withstand 4kV for 1 minute Impulse voltage withstand 6kV 1 2µS waveform Basic current Ib 5A Maximum rated current Imax 45A Operational current range 0 4 Ib Imax Over current withstand 30Imax for 0 01s Operational frequency range 50Hz 10 Internal power consumption 2W Phase 10VA Phase Test ou...

Page 7: ...sφ 0 5L 1 0 Cosφ 0 8C 1 0 8 Description A Display register B Case C Protection cover D Security wire slot Material Register PC flame resistant plastic Case ABS flame resistant plastic Terminal block ABS flame resistant plastic Protection cover ABS flame resistant plastic Note the image on the right might slightly differ from the type you have bought B C A D ...

Page 8: ... the neutral line The connecting wire connecting the device to the outside circuit should be sized in accordance with local regulations for the maximum amount of the current breaker or other overcurrent protection devices used in the circuit An external switch or a circuit breaker should be installed on the supply wires which will be used to disconnect the meter and the device supplying energy It ...

Page 9: ...in accordance with the connection diagram as shown below 1 phase line in L IN 3 phase line out L OUT 4 neutral line in N 6 neutral line out N 20 and 21 Pulse output contact S0 12 Operation 12 1 Consumption indication There is a red LED on the front panel which indicates the consumption measured by the meter When power is consumed the LED will flash The faster the LED flashes the more power is cons...

Page 10: ...ly isolated from the inside circuit It generates pulses in proportion to the measured consumption for purpose of remote reading or accuracy testing The pulse output is a polarity dependent open collector transistor output requiring an external voltage source for correct operation For this external voltage source the voltage Ui should be lower than 27V DC The maximum switching current Imax is 27mA ...

Page 11: ...d personnel familiar with applicable codes and regulations Use insulated tools to maintain or repair the meter Make sure the protection cover is in place after maintenance or repair The case is sealed failure to observe this instruction can result in damage to the meter Problem Possible cause Check Solution The red consumption LED is not flashing PULSE LED There is no load connected to the meter T...

Page 12: ...SOP table contains relevant information for the manufacturer In case you need his support you might be asked to give the SOP number referring to the type of meter you bought Problem Possible cause Check solution No pulse output The pulse output is not supplied with DC power The pulse output is not connected correctly Maybe there is a fault inside the meter Check the external voltage source Ui is 5...