iNels SA2-01B Manual Instructions Download Page 2

Technické parametry / Technical parameters

Všeobecné instrukce / General instructions 

Temperature measuring:
Scope and accuracy of temperature measu-
rement:
Numbers and confi guration:
Switching voltage:Switched load:
Surge current:
Insulation voltage between outputs and 
built-in circuits:
Minimal switching current:
Switching frequency/no load:
Switching frequency/rated load:
Mechanical lifetime:
Electrical lifetime for AC1:
Output indication:
Installation BUS:
Supply voltage/rated current:
Unit status indication:
Max. wire size:
Power outputs:
Operating temperature:
Storage temperature:
Protection degree: 
Control device purpose:
Control device construction:
Characteristics of automatic operation:
Heat and fi re resistance category:
Anti-stroke category (immunity):
Rated impulse voltage:
Overvoltage category:
Pollution degree:
Operating position:
Installation:
Dimensions:
Weight:

Yes, input for external thermo sensor TC, TZ
-20 .. +100°C; 0.5°C from range    
1 x NO contact 16 A/AC1
250 V AC1, 24  V DC
4000 VA/AC1, 384 W/DC
30 A/<3s
3.75kV, 
SELV by EN 60950
100 mA
1200 min

-1

6 min

-1

3 x 10

7

0.7 x 10

5

     

red LED
CIB
27 V DC/40 mA
green LED RUN
0.5 mm

2

 - 1 mm

2

2x conductors CY, section 2.5 mm

2

    

-20 .. +55 °C
-30 .. +70 °C
IP 30
operative control device
individual control device
1.B.E
FR-0
class 2
2.5 kV
III.
2
any
into installation box
49 x 49 x 21 mm
43 g 

ELKO EP, s.r.o.
Palackého 493
769 01 Holešov,Všetuly

 

TECHNICKÁ PODPORA 
E-mail: [email protected] 
Mobil: +420 775 371 522
Tel.: +420 573 514 211, +420 573 514 220
Fax: +420 573 514 227
http://www.inels.cz 
http://www.elkoep.cz

ELKO EP, s.r.o.
Palackého 493
769 01 Holešov,Všetuly
Czech republic

 

Technical support: +420 775 371 532 
E-mail: [email protected]
Tel.:  +420 573 514 211, +420 573 514 220            
Fax:  +420 573 514 227
http://www.inels.com
http://www.elkoep.com

ANO, vstup na externí teplotní senzor TC/TZ
-20 .. +100°C, 0.5°C z rozsahu
1x spínací 16 A/AC1
250 V AC1, 24  V DC
4000 VA/AC1, 384 W/DC
30 A/<3s

3.75kV, SELV dle EN 60950
100 mA
1200 min

-1

6 min

-1

3 x 10

7

0.7 x 10

5

červená LED
CIB
27 V DC/40 mA, ze sběrnice CIB
zelená LED RUN
svorkovnice 0.5 mm

2

 - 1 mm

2

2x vodič CY, průřez 2.5 mm

2

-20 .. +55 °C
-30 .. +70 °C
IP 30
provozní řídící zařízení
samostané řídící zařízení
1.B.E
FR-0
třída 2
2.5 kV
III.
2
libovolná
do instalační krabice
49 x 49 x 21 mm
43 g

Měření teploty:
Rozsah a přesnost měření teploty:
Výstup:
Spínané napětí:
Spínaný výkon:
Špičkový proud:
Izolační napětí mezi reléovými výstupy a 
vnitřními obvody:
Minimální spínaný proud:
Frekvence spínání bez zátěže:
Frekvence spínání se jm. zátěží:
Mechanická životnost:
Elektrická životnost AC1:
Indikace výstupu:
Instalační sběrnice:
Napájecí napětí/jm. proud:
Indikace stavu jednotky:
Datové:
Silové:
Pracovní teplota:
Skladovací teplota:
Stupeň krytí: 
Účel řídícího zařízení:
Konstrukce řídícího zařízení:
Charakteristika automat. působení:
Kategorie odolnosti proti teplu a ohni:
Kategorie (imunita) protirázům:
Jmenovité impulsní napětí:
Kategorie přepětí:
Stupeň znečištění:
Pracovní poloha:
Instalace:
Rozměry:
Hmotnost:

CONNECTION INTO THE SYSTEM
Wires of data bus of INELS system are to be connected to a terminal block of unit CIB+ and CIB-, it I not possible to change the terminals. It is essential to use a twisted pair of wires for data bus. Data 
communication and supply of units are lead in one pair of wires, it is necessary to observe profile for supply wires with regards to voltage loss on the lead and maximal consumed output.
CAPACITY AND CENTRAL UNIT
It is possible to connect two independent CIB buses to a central unitCU2-01M. Such connection is done by terminals CIB1+, CIB1- and CIB2+, CIB2-. To each bus, it is possible to connect up to 32 units, 
meaning in total you can connect up to 64 units directly to a central unit. Other units can be connected by using units MI2-02M, that generate other CIB buses. These are connected to a central unit CU 
by a communication bus TCL2. In total you can connect up to 2 MI2-02M units to one central unit.  
COMMUNICATION BUS OF THE SYSTEM
The bus has to be made a cable which is made of twisted pair of wires for data bus of the system with minimal profile of wires 0.5 mm

2

.  Shielded cable needs to be used in case the bus cables are installed 

in an environment with a possibility of electromagnetic interference (e.g. in case of side-run with power lead, close to electric machines and devices, when passing NN through a switchboard etc.).  
The bus cable is to be installed in accordance with its mechanic features, that are given by its manufacturer (into a conduit/rail, under a plaster, into a ground, hanging etc.) To increase its mechanical 
immunity we recommend installation of the cable into an electro-installation conduit of a sufficient profile. 
The total length of the bus for 1CU2-01M, or MI2-02M, can be 1100 m (550 m for each bus).  Topology of communication bus CIB is free except for circle topology.
SUPPLYING THE SYSTEM
To supply system we recommend to use power supplies of company ELKO EP PS-100/INELS, DR-60-24. The number of power supplies in the system depends on the sum of rated currents of connected 
units with a sufficient reserve. Installation of higher number of power supplies on a large bus eliminates voltage loss on a long lead. In case the system contains a system of electric safety signalization, 
we recommend to use a backed-up power supply with a charger PS-100/INELS in a cover with protective contact. 
GENERAL INFORMATION
The unit is able to be operated individually without a central unit but very limited on functions.  To use all the functions of the unit it is necessary to connect it to a central unit CU2-01M, or to a system 
that already contains this unit and enlarge thus the system functions. All parameters are set by a central unit CU2-01M in software INELS Designer and Manager. On the front panel there are LED diodes 
to indicate presence of supply voltage, communication with a central unit CU2-01M.

PřIPOJENí DO SYSTéMU
Vodiče datové sběrnice systému INELS se připojují na svorkovnici jednotky CIB+ a CIB-, přičemž není možné svorky vzájemně zaměnit. Pro datovou sběrnici je nutno použít kroucený pár vodičů. Datová 
komunikace i napájení jednotek jsou vedeny v jednom páru vodičů, přičemž je nutné dodržet průřez pro napájecí vodiče s ohledem na úbytek napětí na vedení a maximální odebíraný výkon.
KAPACITA A CENTRÁLNí JEDNOTKA
K centrální jednotce CU2-01M lze připojit dvě samostatné sběrnice CIB prostřednictvím svorek CIB1+, CIB1- a CIB2+, CIB2-. Na každou sběrnici lze připojit až 32 jednotek, celkově lze tedy přímo k 
centrální jednotce připojit až 64 jednotek. Další jednotky lze připojit pomocí jednotek MI2-02M, které generují další sběrnice CIB. Tyto se připojují k jednotce CU2-01M přes komunikační sběrnici TCL2 a 
celkem je možno připojit až 2 jednotky MI2-02M k CU2-01M. 
KOMUNIKAčNí SBěRNICE SYSTéMU
Sběrnice musí být provedena kabelem, který obsahuje kroucený pár vodičů pro datovou sběrnici systému s minimálním průřezem vodičů 0.5 mm

2

.  Stíněný kabel je nutné použít v případě instalace 

kabelů sběrnice do prostředí s možností elektromagnetických interferencí (např. při souběhu se silovým vedením, v blízkosti elektrických strojů a přístrojů, při průchodu NN rozvaděčem apod).  
Sběrnicový kabel se instaluje v souladu s jeho mechanickými vlastnostmi, které udává výrobce (do trubky/lišty, pod omítku, do země, závěsný apod.) Pro zvýšení mechanické odolnosti kabelů 
doporučujeme vždy kabel instalovat do elektroinstalační trubky vhodného průměru.
Celková délka vedení sběrnice pro 1CU2-01M, popřípadě MI2-02M, může být 1100 m (550 m pro každou sběrnici). 
Topologie komunikační sběrnice CIB je volná s vyjímkou topologie kruhu.
NAPÁJENí SYSTéMU
K napájení jednotek systému doporučujeme napájecí zdroje ELKO EP PS-50/27, DR-60-24, PS-100/INELS. Počet napájecích zdrojů v systému je dán součtem jmenovitých proudů připojených jednotek 
s odpovídající rezervou.  Větší počet zdrojů na rozsáhlé sběrnici eliminuje také úbytek napětí na dlouhém vedení. Pokud je v instalaci použit systém elektrické zabezpečovací signalizace, doporučujeme 
použít zálohovaný zdroj PS100/INELS v krytu s ochranným kontaktem. 
VŠEOBECNé INFORMACE
Jednotka je schopna pracovat jako samostatný prvek bez centrální jednotky jen ve velmi omezeném rozsahu svých funkcí. Pro plnou využitelnost jednotky je nutné aby jednotka byla napojena na 
centrální jednotku systému CU2-01M, nebo na systém, který tuto jednotku již obsahuje, jako jeho rozšíření o další funkce systému.
Všechny parametry jednotky se nastavují přes centrální jednotku CU2-01M  v software INELS Designer and Manager. 
Na předním panelu jednotky jsou LED diody, pro indikaci napájecího napětí, komunikaci s centrální jednotkou CU2-01M a pro indikaci stavu výstupu jednotky.