background image

GSB3-40, GSB3-60, GSB3-80

1/2

+

-

BUS
BUS

+

-

BUS
BUS

Glass wall touch controllers

EN

Characteristics 

- The wall controller with touch controls series GSB3 is a design element (controller) in the system 

iNELS with elegant and comfortable control. Controllers are available in black (e.g. GSB3-40/B) 
and white (e.g. GSB3-40/W) variants.

- Between each pair of touch buttons there is available a pair of indicator LEDs (green, red) to signal 

not only the status of the controlled appliances, but also the status of any sensor or actuator in 
the system.

- At the location of each touch button there is available a blue diode signaling the touching of the 

given button. Touching may be signaled by a vibration impulse or sound tone - selectable in the 
software iDM3.

- Controllers are 4-channels (GSB3-80), 6-channels (GSB3-60) and 8-channels (GSB3-80).
- All versions are in the same dimension as a basic modular wall-switch (94x94 mm), in design 

LOGUS

90

.

- Each controller is equipped with a thermo sensor. It is equipped with two analog-digital inputs 

(AIN/DIN), and it is possible to connect two potentialless contact or an external temperature sen-
sor TC/TZ (for example on fl oor temperature measurement).

- Controllers are equipped with an ambient light intensity sensor. From the basic information from 

the sensor, it is possible to illuminate orientation blue diodes in the touch controls GSB3 or per-
form various actions in the software iDM3, e.g. illuminate light circuits in a hallway, etc.

- Advantages over conventional switches / buttons include space saving, signaling of any output 

system, the ability to measure temperature and also the ability to connect external buttons or 
detectors.

- Each channel (button) can control any actuator (appliance) in the system. It is also possible to 

program various functions or fuction macro (set of functions) to each button. This allows you to 
control several appliances with one button simultaneously.

- Each button (channel) can have diff erent functional modes beside lighting control:
  a) Classic  wall-switch:  - upper button ON, bottom button OFF
  b) Button controller (impulse relay):  - fi rst press ON, second press OFF
  c) Dimmer: - short press – ON/OFF
  d) Time switch: - ON after press, automatically OFF after set time
  e) Setting light scenes – for example: for watching TV:

- shutters down
- main light 30% intensity
- wall-lamps 50% intensity.

- Design series LOGUS

90

 off  ers glass frames in black and white color. These frames goes perfectly 

with GSB3 wall buttons.

• Package includes:

- 2x 031.01 screws  3x20 mm flat head frame

General instrucions

Connection

Thermo sensors TC / TZ 

2x input for fl oating contacts 
(buttons, PIR etc.).

CONNECTION TO THE SYSTEM, INSTALLATION BUS

iNELS3 peripheral units are connected to the system through the BUS installation. Installation BUS 
conductors are connected to the terminal units to BUS+ and BUS- terminals, wires cannot be interchanged. 
For installation of BUS it is necessary to use a cable with a twisted pair of wires with a diameter of at least 
0.8 mm, the recommended cable is iNELS BUS Cable, whose features best meet the requirements of the 
BUS installation. Bearing in mind that in terms of all the properties is it is possible in most cases also use the 
cable JYSTY 1x2x0.8 or JYSTY 2x2x0.8, however it is not recommended as the best option. In the case of a 
cable with two pairs of twisted wires it is not possible to use the second pair of the other for modulated 
signal due to the speed of communications; it is not possible within one cable to use one pair for one 
segment BUS and the second pair for the second segment BUS. For installation of BUS it is vital to ensure 
that it is kept at a distance from the power lines of at least 30 cm and must be installed in accordance with 
its  mechanical  properties.  To  increase  mechanical  resistance  of  cables  we  recommend  installation  into 
a conduit of suitable diameter. BUS topology installation is free except for the ring, wherein each end of 
the bus must terminate at the terminals BUS + and BUS- peripheral unit. While maintaining all the above 
requirements, the maximum length of one segment of the installation BUS can reach up to 550 m. Due 
to the data communication and supply of units in one pair of wires, it is necessary to keep in mind the 
diameter of wires with regards to voltage loss on the lead and the maximum current drawn. The maximum 
length of the BUS applies provided that they comply with the tolerance of the supply voltage.

CAPACITY AND CENTRAL UNIT

It is possible to connect to the central unit CU3-01M or CU3-02M two independent BUSes by means 
of  terminals  BUS1+,  BUS1-  and  BUS2+,  BUS2-.  It  is  possible  to  connect  to  each  BUS  up  to  32  units,  so  it 
is  possible  to  connect  directly  to  the  central  unit  a  total  of  64  units.  It  is  necessary  to  comply  with  the 
requirement of a maximum load of one BUS line - maximum up to 1000 mA current. When connecting 
units which draw greater than 1A, BPS3-01M with 3A sampling can be used. It is the sum of the rated 
currents of the units connected to the BUS line, other units can be connected using the units MI3-02M, 
which generate further BUSes. These are connected to the CU3 unit via the system BUS EBM and you can 
connect a total of 8 units via EBM BUS to the central unit MI3-02M. 

SUPPLYING THE SYSTEM

For supplying power to system units, it is recommended to use the power source of ELKO EP titled PS3-
100/iNELS. We recommend backing up the system with backup batteries connected to the source of 
PS3-100/iNELS (see sample diagram of connecting the control system).

GENERAL INFORMATION

To operate the unit, it is necessary that the unit is connected to a central unit CU3 series, connected to the 
central unit of the system CU3, or to a system that already contains this unit as its expansion to include 
further system.

All unit parameters are set through the central unit CU3-01M in the software iDM3.

There is LED diode on the PCB for indication of supply voltage and communication with the central unit 
series CU3. In case that the RUN diode fl ashes at regular intervals, so there is standard communication 
between the unit and BUS. If the RUN diode lights permanently, so the unit is supplied from BUS, but there 
is no communication between BUS and unit. In case that RUN diode is OFF, so there is no supply voltage 
on the terminals BUS+ and BUS-.

Reviews: