5.1.4 Positioning the magnets in relation to the
reed switches
▪
Open the sliding gate,
▪
attach the tray with the reed switches with
reed switch O (CON2) opposite magnet O.
The reed switch should not be fixed in the
tray. Connect the ohmmeter to the reed
switch. Gently move the reed switch left and
right to determine the middle of its operating
range. Fix the reed switch in place.
▪
Close the sliding gate. Move reed switch Z
(CON1) in the tray and place it opposite
magnet Z. Do not fix the reed switch.
Connect the ohmmeter to the reed switch.
Gently move the reed switch left and right to
determine the middle of its operating range.
Fix the reed switch in place.
5.1.5 Installing and connecting the controller
Install the controller and the tray with reed switches
inside the sliding gate control unit. If this is not
feasible, install the controller and the tray with reed
switches close to the sliding gate control unit. Secure
the controller, the reed switches and the insulated
cables against mechanical damage and weather
conditions.
Fig. 4 shows the connection diagram. Route the
cables to the controller enclosure by the grommets to
ensure proper sealing and arrange in loops to
prevent water ingress.
Connect the OUT output to the manual control input
of the sliding gate control unit.
The controller may be supplied with 12 V DC or 24 V
AC (from the sliding gate control unit or the external
power supply). Fig. 2 shows the wiring diagram for
both cases. Fig. 5 shows 12 V power supply from the
control unit.
The cables must not block the control unit’s
enclosure and must not affect its weather protection
components.
Fig. 4 Controller wiring diagram
5.1.6 Registering and configuring the controller
in InelControl system
To register and configure of the controller in InelControl
system, see “Control unit user manual and InelControl
system configuration”.
The device will be automatically detected by the system.
Press and hold S1 on the controller board for approx. 1
second. If the device is not automatically detected,
change the controller position and try again.
After configuring the controller, check the received signal
level in
Advanced device information
tab in InelControl
app. For correct communication, the level should be min.
-90 dBm
5.2 Sectional gate
Similar to the sliding gate, installation of reed switches is
required.
Fig. 5 shows the operation of reed switches in the
sectional gate.
The magnet is attached to the carriage (C) and the reed
switches are attached to the bar (R).
The reed switches are at a distance that will prevent
nonselective operation. Choose the optimal position of
the reed switches in relation to the magnet (see the
sliding gate section).
Install he controller near the gate control unit. Fig. 4
shows the wiring diagram.
Fig. 5 Operation of open/close switches of the sectional gate:
a)
door
closed
-
reed
switch
Z
closed,
b) door open
– reed switch O closed