SE10F230

Valve actuator for 3-position control

SE10F230 is a valve actuator designed for control of AB Industri-
etechnik valves. For more info, see the product sheet of each valve. 
The actuator can also be combined with other brands of valves using 
adapter kits. The actuator can be operated manually.

Technical data

Supply voltage 

 

230 V AC ±15 %, 50 Hz 

Control signal 

 

3-position 

Max. power consumption   15.3 W / 16.5 VA 
Stroke 

 

10...30 mm 

Stroke time 

 

3 s/mm 

Force  

 

1000 N 

Ambient temperature 

0...50ºC 

Storage temperature 

-40...80°C 

Ambient humidity   

10...90 % RH 

Dimensions 

 

200 x 270 x 135 mm 

Protection class   

IP54

Mounting

If the valve stem lock and valve throat adaptor are not already mounted 
on the valve, mount them. Pull the valve stem out as far as possible. 
Remove the locking bolts and U-bolt from the actuator yoke.

Depress the spring-loaded tab on the drive rod coupling device and fit the 

valve stem into the coupling. Release the tab to connect the valve to the 
actuator.
The position of the yoke on the valve stem adaptor must be adjusted so 
that the U-bolt mounting holes line up with the groove in the valve throat 
adaptor. If the drive rod needs to be moved in or out for this, depress the 
central button of the control knob and turn it clockwise to extend the drive 
rod and counter-clockwise to retract it (see Manual override).

Mount the U-bolt and the nuts. Tighten the nuts until the actuator is firmly 

attached. Disassembly takes place in reverse order.

Mounting positions

   

Wiring

1

2

3

Y1

N

Y2

Y1 sluten = Ställdonsspindeln skjuts ut

Y2 sluten = Ställdonsspindeln dras in

L      N

230V AC

Calibration

Field calibration is not required. When the valve reaches an endpoint 
and the actuator provides nominal positioning force, power to the 
actuator motor is cut automatically.

Manual override

To manually set the valve position, first depress the central part of the 
knob until it clicks in place and remains depressed (1 in the figure). 

The valve position may then be changed manually by turning the 

knob (2 in the figure). Clockwise rotation will extend the drive rod and 

anti-clockwise rotation will retract it. 
To return to normal operation, position the knob so that it is in line with 
the text (Auto) on the cover. Then press down on the outer parts of 

the knob (3 in the figure). The depressed central part will pop out and 

the actuator will return to operation.

 

 

Low Voltage Directive (LVD) standards

This product conforms to the requirements of the European Low Volt-
age Directive (LVD) 2006/95/EC through product standards EN60730-
1:2000 and EN60730-2-14:1997.

EMC emissions & immunity standards

This product conforms to the requirements of the EMC Directive 
2004/108/EC through product standards EN60730-1:2000 and 
EN60730-2-14:1997.

RoHS

This product conforms to the Directive 2011/65/EU of the European 
Parliament and of the Council.

Contact

AB Industrietechnik Srl

Via Julius Durst, 70 - 39042 Bressanone (BZ) - Italy
Tel.  +39 0472/830626 - Fax +39 0472/831840
www.industrietechnik.it - [email protected]

SE10F230

 

11917C JAN 18

EN

1

1

2

3

Y1

N

Y2

Y1 sluten = Ställdonsspindeln skjuts ut

Y2 sluten = Ställdonsspindeln dras in

L      N

230V AC

Y1 circuit closed = Actuator spindle

is extending from the actuator

Y2 circuit closed = Actuator spindle

is retracting into the actuator

90º

90º

Summary of Contents for SE10F230

Page 1: ...1 N Y2 Y1 sluten Ställdonsspindeln skjuts ut Y2 sluten Ställdonsspindeln dras in L N 230V AC Calibration Field calibration is not required When the valve reaches an endpoint and the actuator provides nominal positioning force power to the actuator motor is cut automatically Manual override To manually set the valve position first depress the central part of the knob until it clicks in place and re...

Page 2: ...Circuito Y2 chiuso Il perno dell attuatore si ritrae nell attuatore L N 230V CA Calibrazione della corsa e del finecorsa Grazie alla costruzione che prevede l utilizzo di appositi fermi di fine corsa non è necessario effettuare alcuna calibrazione della corsa e di posizione Quando la valvola raggiunge la posizione estrema viene generata una forza Non appena la forza dell attuatore arriva al livell...

Page 3: ...L N 230V AC Kalibrierung Eine vor Ort Anpassung ist nicht erforderlich Erreicht das Ventil die End position und der Stellantrieb liefert Nennkraft wird der Stellantriebsmotor automatisch abgeschaltet Handbedienung Die Ventilstellung kann manuell eingestellt werden indem der mittlere Teil des Drehknopfes heruntergedrückt wird bis er einrastet 1 in der Abbildung Die Ventilstellung kann durch Drehen ...

Page 4: ...onsspindeln skjuts ut Y2 sluten Ställdonsspindeln dras in L N 230V AC Étalonnage Il n est pas nécessaire d effectuer un étalonnage du champ Lorsque la vanne atteint la butée et que l actionneur fournit une force de réglage nominale l alimentation du moteur se coupe automatiquement Commande manuelle Pour régler manuellement la position de la vanne appuyez sur la partie centrale du bouton jusqu à en...

Reviews: