Radiator circuit control with outdoor curve

The water temperature setpoint is changed according 
to the outdoor temperature. A single PI control loop is 
used. A room temperature sensor can be added to give 
corrective action if the room temperature differs from the 
setpoint.

This control mode requires two sensors, “Supply 
temperature” on AI1 and “Outdoor sensor” on AI2.
A room temperature sensor can also be connected to UI1, 
permitting the room temperature offset to correct the 
supply temperature. Wire UI1 as an analogue input.

3-position control

Instead of the analogue outputs, CMF can be configured 
for 3-position control (increase / decrease). DO1 will 
then be used for the increase signal and DO2 for the 
decrease signal. This option cannot be combined with an 
alarm output.

Domestic hot water control

The water temperature is kept constant by controlling the 
output signal on AO1. A single PID control loop is used. 

This control mode requires a sensor, “Supply water 
temperature”, on AI1

Summary of Contents for CMF10

Page 1: ...essing the knob Models The CMF series comprises two different types CMF5U and CMF10 CMF5U has 5 in outputs and CMF10 has 10 in outputs CMF10 is available in two versions CMF10 with 24 V AC supply voltage CMF10 230 with 230 V AC supply voltage CMF has been developed according to our Ready Steady Go concept which simplifies every step from installation to management Applications CMF10 and CMF10 230 ...

Page 2: ...an symbol control modes 1 2 and 3 only is lit as long as the fan indication input is activated To see the values and status of all in and outputs simply turn the knob counter clockwise until the text I O is displayed and then press it To return to the Base display click on the knob and then turn it clockwise Display handling All setting and configuration is performed using the display and encoder ...

Page 3: ...igital outputs Damper control with settable minimum supply air amount Control of frost protection or frost protection thermostat with manual reset High temperature limit switch Electric heater cool down function Digital scheduler Start stop of fan via built in relay for 230 V AC Digital input for extended running via timer Input for an external setpoint device Alarm management in the display as we...

Page 4: ...ng 2 Cooling 3 Heating Cooling 4 Heating Heating 5 Cooling Cooling 6 Heating Dampers 7 Cooling Dampers 3 position control Instead of the analogue outputs CMF can be configured for 3 position control increase decrease Only the following output choices will then be available Heating Cooling DO1 is used for increase signal and DO2 for decrease This option cannot be combined with alarm output A single...

Page 5: ...sensor can also be connected to UI1 permitting the room temperature offset to correct the supply temperature Wire UI1 as an analogue input 3 position control Instead of the analogue outputs CMF can be configured for 3 position control increase decrease DO1 will then be used for the increase signal and DO2 for the decrease signal This option cannot be combined with an alarm output Domestic hot wate...

Page 6: ...oduct conforms to the requirements of the EMC Directive 2004 108 EC through standards EN 61000 6 1 and EN 61000 6 3 RoHS This product conforms to the Directive 2011 65 EU of the European Parliament and of the Council Inputs Analog inputs Three AI1 PT1000 sensor working range 0 84 C accuracy 0 5 C AI2 PT1000 sensor working range 30 54 C accuracy 0 5 C SPI PT1000 setpoint device working range 0 40 C...

Page 7: ...O1 and AO2 21 AO1 0 10 V DC output 22 AO2 0 10 V DC output 40 DI2 Digital input 41 DI Reference for DI1 and DI2 42 DI1 Digital input 43 UI Reference for UI1 44 UI1 Universal input PT1000 or Digital 50 AGND Reference for AI1 51 AI1 PT1000 temperature sensor input 52 AGND Reference for AI2 SPI 53 AI2 PT1000 temperature sensor input 54 SPI Input PT1000 setpoint device Terminal Designation Operation 0...

Reviews: