EK-WL8-HS/AU
WIRELESS HEAT DETECTOR
WITH BUILD-IN SOUNDER
STFV.425238.038-AU-UM rev. 18
20.08.2020
Page
4
from
8
TESTING
A test alarm can be activated with a magnet, by
holding it for 1 second near the area on the
opposite side of the marks on the detector’s base.
ANALOG DATA
The device provides the translator module with analog data about the current air
temperature and voltage levels on its batteries. This information can be viewed in
the “Streletz-Wizard” software.
By analyzing the voltage levels, you can manage your maintenance procedures
and predict when you will have to replace the batteries. Please refer to the
software manual for full instructions on how to use the program for system
maintenance.
SOUNDER
The
EK-WL8-OS
sounder may generate two tones:
Tone Mode
Frequency
Tone1
3500 Hz
Tone2
2150 Hz
Device has six sound alert modes. You can choose mode by EK-WL8-TRH menu.
Configuration
Maintenance
Radio
Start Addr
Signal line
--ADD NEW--
Edit
Alarm mess.
Cont. tone
Se
le
ct
001 wl8-hs
etc.
WL8-TRH
v x.x/RF v.y
A1
Info
Pulse 1s/1s
Password
000 wl8-trh
Alarm sound
Pulse 2s/2s
Dual 1s/1s
Dual .4s/.4s
Pulse .2s/1.3s
002 wl8-os