General
17 / 121
1.5
Smoke sensors used
Danger
Only those smoke sensors in the device approval and in the list below may be used in the ASD 532 aspirating
smoke detector. The use of third-party detectors voids the ASD 532 approval issued by the manufacturer.
Smoke sensors of the following type can be fitted in the ASD 532 (see also Sec. 4.9 and 6.6.4):
•
SSD 532-1
Alarm sensitivity range 0.5%/m to 10%/m
•
SSD 532-2
Alarm sensitivity range 0.1 %/m to 10%/m
•
SSD 532-3
Alarm sensitivity range 0.02 %/m to 10%/m
The response sensitivity of the concerned smoke sensor can be adjusted within the above specified range. Depending on the
application in accordance with EN 54-20, Class A, B or C, the value is specified via AMB 32 (pre-defined switch positions as
described in Sec. 4.4.4 to 4.4.4.3) or based on planning specifications using the ASD PipeFlow calculation software via the
ASD Config configuration software (see Sec. 7.2.1). The selection of the smoke sensor type with the respective range of sensi-
tivity is based on the information in Sec. 4.4.4.3 or “ASD PipeFlow”.
1.6
Hardware / firmware
The hardware is considered to comprise the complete detector housing and all the units belonging to the ASD 532 aspirating
smoke detector such as sampling pipe and mounting material.
The firmware is located on the
Flash PROM
in the ASD 532. An EEPROM is fitted for storing and saving system-specific pa-
rameters.
Danger
The ASD 532 is to be operated only with the appropriate original firmware from the manufacturer.
Any unauthorised intervention in the firmware or the use of non-original firmware may result in malfunction and/or
in damage to the device. Furthermore, all guarantee and warranty rights with respect to the manufacturer of the
ASD 532 will become null and void as a result.
© Copyright by Securiton
All ASD 532 firmware is subject to the manufacturer’s copyright. Any unauthorised intervention in the firmware, misuse,
copying or unauthorised trade with the firmware represents a breach of copyright and will be subject to legal proceedings.
Notice
A version change or extension of the ASD 532 firmware does not imply a right to an upgrade or new release for
existing ASD 532 systems.
ASD532
Operating
Manual
Summary of Contents for ASD 532
Page 1: ...ASD 532 Aspirating Smoke Detector Operating Manual ...
Page 2: ...2 88 ASD532 Operating Manual ...
Page 6: ...6 121 ASD532 Operating Manual ...
Page 7: ...Document history 7 121 Document history First edition Date 15 10 2015 ASD532 Operating Manual ...