Immergas VICTRIX MAIOR 35 X TT 1 ERP Instruction And Recommendation Booklet Download Page 17

17

1-26

C

53

C

93

1-25

X

INS

TALLER

US

ER

MAINTEN

AN

CE TECHNI

CI

AN

1.17 DUCTING OF FLUES OR 

TECHNICAL SLOTS.

Ducting is an operation through which, via 

the introduction of one or more relevant pipes, 

one achieves a system for the evacuation of the 

combustion products of a gas appliance, made up 

from the coupling of an existing or new ducting 

pipe with a chimney, flue or technical slot (also 

in new buildings) (Fig. 1-26). Ducting requires 

ducts declared to be suitable for the purpose by 

the manufacturer, following the installation and 

user instructions, provided by the manufacturer 

and the requirements of the standards in force.

Immergas ducting system.

 

The Ø 60 rigid and 

Ø 80 flexible “Green Range” ducting systems must 

only be used for domestic use and with Immergas 

condensing boilers.

In any case, ducting operations must respect 

the provisions contained in the standard and in 

current technical regulations; in particular, the 

declaration of conformity must be compiled at 

the end of work and on commissioning of the 

ducted system. The instructions in the project 

or technical report must likewise be followed, in 

cases provided for by the standard and current 

technical regulations. The system or components 

of the system have a technical life complying with 

current standards, provided that:

-  it is used in average atmospheric and environ-

mental conditions, according to current regula-

tions (absence of fumes, dusts or gases that can 

alter the normal thermophysical or chemical 

conditions; existence of temperatures coming 

within the standard range of daily variation, 

etc.).

- Installation and maintenance must be per-

formed according to the indications supplied 

by the manufacturer and in compliance with 

the regulations in force.

- The maximum length specified by the manu-

facturer must be respected; in this regard:

  -  The max. possible length of the Ø 60 flexible 

ducting vertical section is equal to 22 m. This 

length is obtained considering the complete 

Ø 80 exhaust terminal, 1m of Ø 80 pipe in 

exhaust, two 90° Ø 80 bends at boiler outlet.

  - The max. possible length of the Ø 80 flex-

ible ducting vertical section is equal to 30 

m. This length is obtained considering the 

complete exhaust terminal, 1m of Ø 80 pipe 

in exhaust, two 90° Ø 80 bends at boiler outlet 

for connecting to the ducting system and two 

direction changes of the flexible hose inside 

the chimney/technical slot.

  - The maximum possible length of the Ø 80 

rigid ducting vertical section is equal to 30 

m. This length is obtained considering the 

complete Ø 80 exhaust terminal, 1m of Ø 80 

pipe in exhaust, two 90° Ø 80 bends on the 

boiler outlet.

1.18  CONFIGURATION TYPE B, OPEN 

CHAMBER AND FAN ASSISTED FOR 

INDOORS.

The appliance can be installed inside buildings 

in 

23

 or B

53

 mode; in this case, all technical rules 

and national and local regulations in force, must 

be complied with.

- Type B open chamber boilers must not be 

installed in places where commercial, artisan 

or industrial activities take place, which use 

products that may develop volatile vapours 

or substances (e.g. acid vapours, glues, paints, 

solvents, combustibles, etc.), as well as dusts 

(e.g. dust deriving from the working of wood, 

coal fines, cement, etc.), which may be harm-

ful for the components of the appliance and 

jeopardise operation. 

-  In B

23

 and B

53

 configuration the boilers must not 

be installed in bedrooms, bathrooms or bedsits, 

unless otherwise provided for by local regula-

tions in force. They must neither be installed 

in rooms containing solid fuel heat generators 

nor in rooms communicating with said rooms.

- The installation of appliances in B

23

 and B

53

 

configurations are only recommended in places 

that are not lived in and which are permanently 

ventilated.

The suitable kit referred to in paragraph 1.12 

must be used for installation.

1.19  FLUE GAS EXHAUST TO FLUE/

CHIMNEY.

Flue exhaust does not necessarily have to be 

connected to a branched type traditional flue. 

The flue exhaust, for boiler clots installed in C 

configuration, can be connected to a special 

LAS type multiple flue. For B configurations, 

exhaust is only allowed into individual chimney 

or directly into the external atmosphere via a 

suitable terminal, unless otherwise provided 

for by local regulations in force. The multiple 

flues and the combined flues must also only be 

connected to type C appliances of the same type 

(condensing), having nominal heat inputs that do 

not differ by more than 30% less with respect to 

the maximum that can be attached and powered 

by the same fuel. The thermo-fluid dynamic 

features (flue flow rate, % of carbon dioxide, % 

humidity etc....) of the appliances attached to 

the same multiple flues or combined flues, must 

not differ by more than 10% with respect to the 

average boiler attached. Multiple and combined 

flues must be specially designed according to 

the calculation method and requirements of the 

technical standards in force, by a professionally 

qualified company. Chimney or flue sections for 

connection of the flue exhaust pipe must comply 

with requisites of technical standards in force.

1.20  FLUES, CHIMNEYS, CHIMNEY POTS 

AND TERMINALS.

The flues, chimneys and chimney pots for the 

evacuation of combustion products must be in 

compliance with applicable standards. Chimneys 

and roof-installed exhaust terminals must com-

ply with the outlet height and with the distance 

from technical volumes set forth by the technical 

standards in force.

Positioning the wall flue exhaust terminals.

 The 

wall flue exhaust terminals must:
- be installed on external perimeter walls of the 

building;

- be positioned according to the minimum dis-

tances specified in current technical standards.

STD.002549/004

Summary of Contents for VICTRIX MAIOR 35 X TT 1 ERP

Page 1: ...VICTRIX MAIOR 35 X TT 1 ERP IE Instruction and recommendation booklet 1 038660ENG STD 002549 004...

Page 2: ...STD 002549 004...

Page 3: ...ified in the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits establis...

Page 4: ...ce 21 2 2 General warnings 21 2 3 Control panel 21 2 4 Using the boiler 22 2 5 Troubleshooting 22 2 6 Information menu 25 2 7 Boiler shutdown 25 2 8 Restore central heating system pressure 25 2 9 Syst...

Page 5: ...removal connections Keep all flamma ble objects away from the appliance paper rags plastic polystyrene etc Do not place household appliances underneath the boiler as they could be damaged if the safet...

Page 6: ...kept An aqueous solution must be made with potential pollution class of water 2 EN 1717 2002 or local regula tions in force Attention the excessive use of glycol could jeopardise the proper functioni...

Page 7: ...ipes radiators etc with special pickling or descaling products to remove any deposits that could compromise correct boiler operation A treatment of the heating and water system water is required in co...

Page 8: ...stats are connected with 2 wires only Carefully read the user and assembly instructions contained in the acces sory kit On Off Immergas digital chrono thermostat The chrono thermostat allows set two r...

Page 9: ...ystem flow temperature to be automatically decreased when the external temperature increases in order to adjust the heat supplied to the system according to the change in external temperature The exte...

Page 10: ...owed cor responds to the resistance encountered with the maximum allowed pipe length for each type of Terminal Kit This information allows calculations to be made to verify the possibility of setting...

Page 11: ...nd Exhaust 16 3 m 2 5 Intake m 18 7 Exhaust m 4 9 m 7 7 Exhaust m 13 6 Concentric vertical intake exhaust terminal 60 100 Intake and Exhaust 9 m 1 4 Intake m 10 3 Exhaust m 2 7 m 4 3 Exhaust m 7 5 Pip...

Page 12: ...the 2 previously removed screws Install the 80 outlet flange on the central hole of the boiler taking care to insert the gasket supplied with the kit and tighten by means of the screws provided Insta...

Page 13: ...cular projections down wards in contact with the boiler flange and tighten using the screws present in the kit Fit the 60 100 3 concentric terminal pipe with the male side smooth to the female side of...

Page 14: ...up to the end stop making sure that the wall sealing plate has been fitted 3 this will ensure sealing and joining of the elements making up the kit NOTE when the boiler is installed in areas where ve...

Page 15: ...the flat flange present in the lateral hole with respect to the central one ac cording to needs and replace it with the flange 3 positioningthegasket 2 alreadypresentin the boiler and tighten using t...

Page 16: ...a The dimensions of the shafts must ensure a minimum gap between the outer wall of the smoke duct and the inner wall of the shaft 30 mm for circular section shafts and 20 mm in the event of a square s...

Page 17: ...uildings in 23 or B53 mode in this case all technical rules and national and local regulations in force must be complied with Type B open chamber boilers must not be installed in places where commerci...

Page 18: ...ated water To prevent corrosion the water system s PH should be between 6 5 and 8 5 Check the maximum content of chlorides which should be less than 250 mg l N B for quantities and methods of use of w...

Page 19: ...valve kits with or without inspection filter on request The boiler is designed for installation of system interception cocks to be placed on flow and return pipes of the connection assembly This kit i...

Page 20: ...7 Manual air vent valve 8 Delivery probe 9 Ignition detection electrode 10 Flue probe 11 Sample points air A flue gas F 12 Burner cover 13 Safety flow probe 14 Condensation module 15 Fan 16 Return pr...

Page 21: ...prohibited For safety purposes check that the concentric air intake flue exhaust terminal if fitted is not blocked If temporary shutdown of the boiler is required proceed as follows a drain the heati...

Page 22: ...external probe present the relative symbol 18 will appear on the display In the central heating phase if the temperature of the water contained in the system is sufficient to heat the radiators the b...

Page 23: ...er flame switches off unexpectedly a new attempt at ignition is performed and if normal conditions are restored the boiler does not have to be reset If normal conditions are restored the boiler restar...

Page 24: ...e has been detected The boiler does not start 1 88 Block gas valve control A malfunction of one of the components that controls the gas valve has been detected The boiler does not start 1 89 Combustio...

Page 25: ...ntly filling must be car ried out with suitably treated water to eliminate hardness that can cause lime scale 2 11 CASE CLEANING Use damp cloths and neutral detergent to clean the boiler casing Never...

Page 26: ...eck that the intake and or exhaust terminals are not blocked ensure activation of all adjustment devices checktheproductionofDHW whentheboiler is connected to an external storage tank unit check seali...

Page 27: ...or X5 is used for the connection to the relay board The connector X6 is for connection to a personal computer The connector X8 is used for software updating operations Key A19 Removable memory B1 Boil...

Page 28: ...are within the set limits The factory set pressure values of the expansion vessel must be 1 0 bar the value of system pressure must be between 1 and 1 2 bar Noise due to air inside the condensation mo...

Page 29: ...position Fig 3 5 and press the Reset button for about 8 seconds until the chimney sweep function is activated then press the summer winter button within 3 seconds Nominalheatoutput with the function...

Page 30: ...is activated then press the info button within 3 seconds Once the function is active the boiler sequential ly carries out the procedures required to calibrate the appliance with the nominal intermedia...

Page 31: ...E62 will appear and complete calibration will be required Menu G This menu is reserved for the air gas control settings and it features two sub menus n and S relating to fan and gas valve control set...

Page 32: ...neral alarm 2 CH phase active 3 External gas valve power supply 4 Secondary zone control from TA on relay P C B contact 5 Heat pump 6 Do not use on this boiler model 7 Do not use on this boiler model...

Page 33: ...On 5 C Off 0 C 2 t3 Not used on this boiler model t4 Not used on this boiler model t5 Central heating ignitions timer The boiler has electronic timing which prevents the burner from igniting too ofte...

Page 34: ...heck power supply Incaseoffunctioningindomestichotwa Id Parameter Parameter Description Range Default Customised value F0 Equivalent length flue Defines the length of the flue see par 3 12 0 2 0 F1 No...

Page 35: ...integrityoftheelectri cal system and in particular supply voltage cables must be inside the fairleads there must be no traces of blackening or burning Check ignition and operation Check correct calibr...

Page 36: ...a 2 Press the hooks inwards which block the lower grid b 3 remove the grid b Front panel Fig 3 15b 4 Open the protection door e1 pulling it towards you 5 Remove the cover caps c and loosen screws d 6...

Page 37: ...USER MAINTENANCE TECHNICIAN Ref X Control panel Fig 3 15d 9 Press the hooks on the side of the control panel i 10 Tilt the control panel i towards you Sides Fig 3 15e 11 Loosen screws k of side faste...

Page 38: ...URNER GAS FLOW RATE BURNER GAS FLOW RATE kW kcal h m3 h kg h 34 2 29412 99 3 70 2 71 33 5 28810 97 3 62 2 66 32 5 27950 94 3 51 2 58 31 5 27090 91 3 40 2 50 30 5 26230 88 3 29 2 42 29 5 25370 85 3 19...

Page 39: ...80 60 C 0 24 0 10 Heat loss at flue with burner On Off 80 60 C 0 01 2 00 Central heating circuit max operating pressure bar 3 0 Maximum heating temperature C 90 Adjustable heating temperature max oper...

Page 40: ...l Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn max CH maximum heat input Pn...

Page 41: ...1 kW At partial load elmin 0 012 kW Ignition burner energy consumption Pign 0 000 kW In standby mode PSB 0 004 kW Emissions of nitrogen oxides NOX 24 mg kWh For mixed central heating appliances Stated...

Page 42: ...ementary heat pump From fiche of heat pump Solar contribution and Supplementary heat pump Select smaller value Boiler and supplementary heat pump installed with low temperature heat emitters at 35 C F...

Page 43: ...energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficiency is influenced by further facto...

Page 44: ...ution From fiche of solar device 1 I 2 1 1 x I 10 x II III I Auxiliary electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100 115 123...

Page 45: ...nder colder and warmer climate conditions Colder 0 2 x Warmer 0 4 x Declared load profile Solar contribution From fiche of solar device 1 ___ 2 1 1 x ___ 10 x ____ ____ ____ Auxiliary electricity 3 G...

Page 46: ...46 STD 002549 004...

Page 47: ...47 STD 002549 004...

Page 48: ...S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038660ENG rev ST 001863 004 08 18 Inglese per IRLA...

Reviews: