• Use and operation.
-  Start-up display.

  Every time power is supplied to the appliance, 

the display will activate all symbols for 2 sec-

onds:

  while in the next 5 seconds, the display will 

indicate the board software version:

  After which, the following information regard-

ing the type of system will be displayed, the 

temperature of the solar collector (1 ÷ 170°C 

upper digit) and the temperature of the storage 

tank probe (1 ÷ 125°C lower digit): 

 Functioning.

  For the description of the parameters, refer to 

the table in the previous paragraph

 - 

OFF mode.

 By pressing the (

) key for 3 

seconds, the appliance switches to off mode 

(also in the event of anomalies). In this way, 

it is not operational and the display shows 

off. Only the anti-freeze protection and the 

pump anti-block remain active. 

 

-  Solar pump functioning.

    The pump activates and deactivates automati-

cally when it is set in On/Off mode.

  

Activation: 

the solar pump will be activated 

by the board if the following conditions occur 

at the same time: 

    T tank < PAR15 – PAR16 
  and
    Solar collector T - tank T > PAR16
  

Disabling:

 the board disables the solar pump 

if one of the following conditions occurs:

    Tank T > PAR 15
  or
    Solar collector T< tank T + PAR 22
  

Manual mode:

 the pump can be set in On 

mode (always on) or Off mode (always off). 

In the event of manual setting, the protection 

functions are inhibited.

 - 

Solar manifold cooling function

. This func-

tion is used to manage the pump in the event 

of overheating of the solar panel according to 

the following table:

Description

Condition

Solar pump 

activation

PAR 15 < tank T < PAR 18

+

Solar collector T > PAR 17 - PAR 19

Solar pump 

deactivation

Solar collector T (PAR 17 - PAR 

19) -1°C

or

Tank T ≥ PAR 18 +1°C

or

Solar collector T > PAR 17

(reactivates with solar collector T < 

PAR17 -1°C)

    With parameter 19=0, the solar collector 

cooling function is deactivated; the following 

conditions remain active:

    Solar collector T > PAR17 => Solar pump off
    Solar collector T < PAR17– 1°C => Solar 

pump on

 - 

Cold solar manifold recognition function.

 

The board will disable the solar pump (pre-

sent only with return probe) when:

    Solar collector T– solar collector return T < 

PAR 21

 - 

Solar manifold anti-freeze function.

 The 

Solar Pump activates when:

    Solar collector T < PAR 23 
    The board will not deactivate the solar pump 

until: 

    Solar collector T > PAR 23 + 1°C 
  

Attention:

 the default anti-freeze function is 

disabled PAR 23=0

 - 

Solar pump anti-block function.

 After 24 

hours of inactivity, the system pumps are 

activated for 3 seconds.

 - 

Diverter valve anti-block function.

 After 

24 hours of inactivity, the diverter valve will 

be activated for 5 seconds (in systems fitted 

with the diverter valve).

 - 

Priority solar function.

 The function is ac-

tive when: 

    DHW inhibition probe T (PAR 31 - PAR 33) 

< DHW set (parallel integration) 

    DHW inhibition probe T (PAR 31 - PAR 33) 

< DHW set (priority integration) and solar 

loading pump in off for a time > 5 minutes

• Anomalies.

The following table describes the possible anoma-

lous conditions that will be displayed on the basis 

of the system ration selected. 

The possible functioning error conditions are 

displayed on the user interface display.

If an anomaly should occur, the (

) symbol 

starts to flash as well as the back light (anomaly).

If a no communication anomaly should occur, 
the (

) + (

) symbols start to flash as 

well as the back light (communication anomaly). 

Description of anomaly

Fault code

S1 NTC sensor fault

81

S2 NTC sensor fault

82

S3 T1000 sensor fault

83

Solar pump off

87

- Anomaly 81 NTC Sensor faulty: the sensor 

fault, i.e. a short circuit or open circuit, disables 

the Solar Pump (active system protection). The 

protection is deactivated immediately when 

this fault is resolved.

- Anomaly 82 NTC Sensor faulty: the sensor 

fault, i.e. a short circuit or open circuit, disables 

the Solar Pump (active system protection). The 

protection is deactivated immediately when 

this fault is resolved.

- Anomaly 83 PT1000 Sensor faulty: the sensor 

fault, i.e. a short circuit or open circuit, disables 

the Solar Pump (active system protection). The 

protection is deactivated immediately when 

this fault is resolved.

-  Solar pump Off: the solar control unit indicates 

that the solar pump is in forced Off mode 

(parameter 24).

 

• Technical data.

Power Supply: ...................230 Vac + 10% ÷ 15%
Frequency: ...........................................50 Hz ±5%
Mains (PF1): .......................3.15 AF (rapid) 5x20
Free contact outputs: .................5A 30 Vdc relay,
    

10 A 250 Vdc

   (Maximum charge allowed: 0.25 A 230 Vac)

Summary of Contents for UB INOX SOLAR 200 V2

Page 1: ...UB INOX SOLAR 200 V2 Storage tank unit IE Instruction and recommendation booklet 1 041261ENG ...

Page 2: ......

Page 3: ...on it is necessary to comply with the provisions specified in the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits established by the Law Installation and maintenance must be performed in compliance with the regulations in force according to the manufacturer s instructi...

Page 4: ... pump solar heating system 8 1 12 Commissioning 9 1 13 Filling the solar circuit system 9 1 14 Solar control unit user instructions 10 1 15 Main components 13 1 16 Kits available on request 13 2 Use and maintenance instructions 14 2 1 Cleaning and maintenance 14 2 2 Emptying the storage tank unit 14 2 3 Cleaning the case 14 2 4 Decommissioning 14 2 5 Control panel 14 3 Checks and maintenance 15 3 ...

Page 5: ...t operation turn the appliance off and contact an authorised company e g the Authorised Tech nical Assistance centre which has specifically trained staff and original spare parts Do not attempt to modify or repair the appliance alone Failuretocomplywiththeaboveimpliespersonal responsibility and invalidates the warranty Installation standards these storage tanks have been designed for floor install...

Page 6: ... tank unit Attention after the connections have bee made the new system layout must be set on the solar control unit as follows press the i key for about 10 seconds use the scrolling keys to find parameter 27 system configuration press the i key for about 2 seconds upon accessing parameter 27 you will find that configuration 1 is set use the scrolling keys to select configuration 2 press the i key...

Page 7: ...to the boiler instruction book 1 10 MAIN SOLAR CIRCULATION UNIT COMPONENTS The pump unit allows you to connect the storage tank to the solar manifold making the water cir culateaccordingtotherequestofthecontrolunit Hydraulic circuit resistance Head kPa Flow rate l h Head m c a A Storage tank unit hydraulic circuit resistance Key 1 Solar pump 2 Non return valve thermometer and cock 3 Valve drain fi...

Page 8: ...ontrol to set advanced functions For proper op eration one must select the most suitable type of operation for the system and select a speed in the available range with a focus on energy savings Display of operation status During normal operation the status LED 2 is on green flashing FL when it is in stand by the four yellow LEDs 3 indicate circulator absorption according to the following table Ci...

Page 9: ...the roof at a hypothetical height of 6 m the distance to be calculated is 6 m x 0 1 bar 0 6 bar therefore the expansion vessel must be charged to 2 0 6 2 6 bar Hydraulic unit safety valve There is a safety valve present on the hydraulic unit that protects the system from an excessive increase in pressure This valve intervenes by discharging the liquid contained in the circuit when the pressure rea...

Page 10: ...Otherwise press to exit In this case the value set will not be memorised but the previ ous one will be kept To exit the parameter menu press the button once or wait 60 seconds without press ing any keys 6 Eliminate any air in the solar circuit preferably using the so called pressure shot method which consists in raising the filling pressure of the circuit followed by a quick opening of the return ...

Page 11: ...re C 90 160 C 140 C 18 Tank Maximum Temperature C 70 95 C 80 C 19 Value of the temperature differential between the solar collector maximum temperature PAR 17 and the solar collector temperature above which the solar collector cooling func tion activates Solar collector cooling function 0 Function deactivated 0 20 C 0 20 Diverter functioning 0 Off 1 Auto 2 On 0 2 1 21 Value of the Δ flow return te...

Page 12: ...ly with return probe when Solar collector T solar collector return T PAR 21 Solar manifold anti freeze function The Solar Pump activates when Solar collector T PAR 23 The board will not deactivate the solar pump until Solar collector T PAR 23 1 C Attention the default anti freeze function is disabled PAR 23 0 Solar pump anti block function After 24 hours of inactivity the system pumps are activate...

Page 13: ...s 16 Solar panel probe 17 Storage tank electric connections terminal board 1 16 KITS AVAILABLE ON REQUEST Recirculation kit on request The storage tank unit is prepared for application of the pump kit Immergas supplies a series of fittings and attachments that allow connection between the storage tank unit and domestic hot water system The pump kit attachment is also envi sioned on the template El...

Page 14: ...horised local firm 2 2 EMPTYING THE STORAGE TANK UNIT To drain the storage tank use the special drain ing valve in the lower part of the storage tank Fig 1 12 part 8 Before draining ensure that the DHW inlet valve is closed 2 3 CLEANING THE CASE Use damp cloths and neutral detergent to clean the storage tank casing Never use abrasive or powder detergents 2 5 CONTROL PANEL Key 1 Solar control unit ...

Page 15: ...filter 11 One way valve OV 15 Optional 12 Cold water inlet cock 13 One way solar valve 14 6 bar safety valve 15 Shut off valve with thermometer 16 Solar expansion vessel 17 Solar pump 18 Flow meter 19 Domestic hot water probe 20 Domestic hot water unabling probe 21 Stainless steel coil that can be coupled to solar panels 22 Solar system draining valve 23 Solar panel probe AC Domestic hot water out...

Page 16: ...r the DHW regulation NTC probe Check the integrity of the storage tank Magne sium anode Check the state of the internal coil Check for any slurry deposits on the bottom of the storage tank Key A12 Solar management control unit B2 Domestic hot water probe NTC B11 Solar manifold probe PT1000 B12 Solar storage tank probe NTC B19 DHW inhibition probe NTC B20 Solar manifold return probe PT1000 Optional...

Page 17: ...t models remove the lid 1 by pulling it upwards undo the screws 2 and pull the front panel outwards 3 undo the screws 4 of the sides 5 on the top and in the lower part of the sides themselves After having released them from the screws they can be removed by pulling them forward and then upwards 3 5 REPLACING THE ANODE Themagnesiumanodemustbereplacedannually Fig 1 12 part 5 present in the storage t...

Page 18: ... h 1140 1140 Coil head loss at 1000 l h kPa m H2 O 12 3 1 25 Central heating side maximum pressure bar 6 Central heating side maximum temperature C 90 Solar heat exchange maximum output kW 23 8 CH heat exchange maximum output kW 26 5 Full weight kg 310 67 Empty weight kg 106 1 Total water content l 204 57 Solar circuit maximum pressure bar 6 Total volume solar expansion vessel l 13 46 Solar expans...

Page 19: ...19 A A B C D E F 78W 199L C UB INOX SOLAR 200 V2 2017 812 2013 3 7 PRODUCT SHEET IN COMPLIANCE WITH REGULATION 812 2013 ...

Page 20: ...20 ...

Page 21: ...21 ...

Page 22: ...22 ...

Page 23: ...23 ...

Page 24: ...immergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 041261ENG rev ST 003316 000 09 17 Inglese per IRLANDA IE ...

Reviews: