2. MODULATING TEMPERATURE CONTROLLER KIT
The controllers have two independent clean contacts for
controlling a refrigerator unit, a boiler and a presence input.
The 2 tube versions have a 230V output to power the
summer and winter solenoid valve.
The 10 kΩ water temperature probe positioned in the
compartment on the battery regulations the minimum level
when heating (30°C) and the maximum level when cooling
(20°C).
The board also has a function when there is no water
probe, in such cases the fan stop thresholds are ignored.
Slide the control panel into its housing in the upper part
of the device and fix it with the two fixing screws (ref. A).
To install the connection box:
-
open the box (ref. B);
-
lock the lower tooth into its hole (ref. C) on the side of
the device;
-
hook the upper part of the box to the side (ref. D);
-
fix it with the two fixing screws (ref. E);
-
connect the grounding cable to the fan coil body (ref. M)
using the fixing screws (the minimum force that must be
applied for tightening screws must be around 2N);
-
connect the fast connector of the MOTOR to the other
on the board (ref. I) *;
-
on the two GRID block terminals (ref. L) there is a bridge
which must not be removed.
-
For other versions, remove the bridge and connect the
two terminals originating on the grill safety microswitch*;
-
connect the water probe to the H2 connector on the
device.
The water temperature probe controls the temperature
inside the batteries and determines when the fan starts
according to pre-set parameters (minimum operation
in winder and maximum in summer).** Check that
they are correctly inserted into the compartment on
the battery.
-
Connect the electrics, tidy cables and fix them with
the three clevises supplied (ref. G);
-
close the box with the 4 screws (ref. H);
-
refit the vanity plate on the side of the unit;
-
tighten the upper screws on the control panel;
-
place the screw head covers in their housing on the
control panel;
*
For versions with hydraulic connections on the right,
refer to the relevant paragraph
** The regulation also works without a water probe
connected
2.1 Assembly, set-up and connection
2.2 Assembly
Summary of Contents for HYDRO FS
Page 1: ...HYDRO FS IE Instruction booklet and warning 1 041956ENG...
Page 4: ...4 12 Troubleshooting 48 12 1 Table of anomalies and remedies 48...
Page 20: ...20 Load losses based on the adjustment of the lockshield present in all kits...
Page 23: ...23 Diagram of load losses of deviator valve present in kit in completely closed position...
Page 49: ...49...
Page 50: ...50...
Page 51: ...51...