MAGIS HERCULES PRO
35
To access the “assistance menu”, press the “MENU” button.
Access the submenu “General settings” and select “Access lev-
el”.
Insert the relative access code and customise the parameters
described below according to your requirements.
To save the change of the parameters described below, press
the “OK” button.
Exit the “assistance menu” waiting 4 minutes or enter the ap-
propriate access code for the “user menu”.
You can exit the assistance menu by entering the appropriate
access code under the “Access level” item and selecting the
item:
Type of access/User.
At the end, press “OK” to confirm.
After 4 minutes without making any changes in the “Assis-
tance” menu, the system automatically goes back to the “User”
menu.
MENU/
GENERAL SETTINGS
Menu item
Description
Range
Factory setting
Allows to reset all parameters with factory values.
Yes/No
MENU/
ASSISTANCE
Menu item
Description
System definition
Sub-menu to define the devices connected to the system.
Heat pump
Heat pump operating parameters sub-menu.
Integration
System integration setting sub-menu.
Manual drives
Submenu for load operation check.
Special parameters
Parameters for various uses.
MENU/ASSISTANCE/
SYSTEM DEFINITION
Menu item
Description
Range
Default
Number of zones
Defines the number of zones present.
1-3
1
Main zone
Defines the main zone of the system in which the remote panel will be
used.
1 - 2
1
External probe
This defines the type of external probe enabled.
IU=indoor unit, OU = outdoor condensing unit.
OU/IU
OU
Correc. External probe Correction of the external probe value.
-9 +9
0
Photovoltaic function
Enables the operation combined with a photovoltaic system.
Yes / No
No
System supervision
Enabling connection to Dominus or System supervisor.
NO/Domin/
BMS
No
Activation time
Waiting time before activation of the system setpoint correction.
1 - 120
20
Increase time
Time interval for the increase or decrease of 1 °C of correction of the sys-
tem setpoint.
1 - 20
5
Central heating
max correction
Max correction during central heating mode.
0 - 10
0
Cooling
max correction
Max correction during cooling mode.
-10 - 0
0