15.6
Installation instructions for SM BLITZ lightning protection modules
Basically, there are two potential sources of risk in the field of environmental measurement
technology: transmission lines and sensors or network devices. Lightning protection modules
should always be installed at the beginning and at the end of a circuit in order to protect the
electronics from excess voltage (Attention: SM-Blitz modules have a protected and an unpro-
tected side).
The SM-BLITZ lightning protection module has to be grounded using a ground conductor with a
wire cross- section of at least 6 mm
2
screwed to the long side of the module. A 2-metre long
grounding rod may serve as a ground conductor. Grounding is optimal when the grounding rod
is in direct contact with ground water.
15.7
Conclusion
Only limited protection against excess voltage is possible where natural phenomenon such as
lightning strikes are concerned. Direct lightning strikes may cause damage nevertheless.
If you have any questions regarding lightning protection please do not hesitate to contact us.