15
Electronic Pressure Sensor 54D
Operation manual
7503761000000050 05/2019
9.3.2 Set damping for the switching outputs
►
Select [dAP] and set the value.
dAP value = response time between pressure change and change of the
switching status in milliseconds.
The following fixed values can be set; they define the switching frequency (f in
Hz) of the output:
dAP 6
10
30
60
100 250 500 1000
2000
f
80
50
16
8
5
2
1
0,5
0,25
9.3.3 Configuration of the display
►
Select [diS] and set the update rate and orientation of the display:
[d1]: update of the measured values every 50 ms.
[d2]: update of the measured values every 200 ms.
[d3]: update of the measured values every 600 ms.
[Ph]: display of the pressure peaks remains for a short time (peak hold).
[rd1], [rd2], [rd3]: display as for d1, d2, d3; rotated by 180°.
[OFF]: the display is switched off in the operating mode
.
►
Select [cLor] and define the colour of the digital display:
[r-on]: display = red if output 1 is switched; display = green if output 1 is not
switched.
[G-on]: display = green if output 1 is switched; display = red if output 1 is not
switched.
[red]: the colour of the display is red / does not change.
[Gren]: the colour of the display is green / does not change.