7
CONTO D6
Three-phase energy meter
Installation manual
•
Installationsanweisungen
• Installation • Installation
• Recommendations
• Avoid proximity to systems which generate
electromagnetic interference.
•
Empfehlung
•
Nähe zu Generatorsystemen vermeiden
elektromagnetische Störungen.
•
Connection
For the maximum terminal torque see the table
•
Anschluss
Das maximale Anzugsmoment der Klemmen finden
Sie in der Tabelle
MAX
2
1 x 16 mm
8 mm
2
1 x 16 mm
2
1 x 16 mm
Recommended
torque 1Nm
Recommended
torque 3Nm
Recommended
torque 0,2Nm
0,8 x 4mm
197...480 V~ (three phase)
CAT III
I = 0,5 A I
min
I
tr
b
= 10 A I
= 125 A
= 1A
max
I
Wh: 1 (E , EN 62053-21)
a
varh: 1 (E
, EN 62053-23)
rv
cl.
RS485 Modbus
COM
U
MAX
2
1 x 35 mm
8 mm
2
1 x 35 mm
2
1 x 50 mm
COMBI PZ2
N
MAX
2
1 x 1 mm
8 mm
2
1 x 1 mm
2
1 x 1,5 mm
0,5 x 2,5mm
E
RS485
(-5°C) - (55°C)
L1-L2-L3
B (EN 50470-1, -3)
CE6DT125.
CE6DMID5.
5 Wh/imp.
LED
L1
3
L2
6
L3
9
L1
1
N
11
L2
4
L3
7
•
Auxiliary supply:
derived from the voltage terminals (terminals
U1, U2, U3, N)
•
Hilfsversorgung:
abgeleitet von den Spannungsanschlüssen (Klemmen U1, U2, U3, N)
IF4E011/SXIIP
CE6DT1256
CE6DMID56
CE6DT1256
CE6DMID56
CE6DT1256
CE6DMID56
+ – SG
R
T
(2)
+ – SG
+ – SG
+ – SG
N°1
N°2
N°n
ETHERNET
RJ45
RS-485
(2)
(3)
•
RS485 wiring diagram
•
Anschlussbilder RS485
(3)
Ethernet: Cat. 6 (FTP/UTP)
(1)
max. 1000 m Cat. 6
(FTP/UTP)
max. 50 m
(2)
•
Resistance not furnished to be connected between "+ and -" of the 1st and last device of the line
•
Der Widerstand wird nicht für die Verbindung zwischen "+ und -" des ersten und letzten Geräts der Leitung geliefert
Modbus Address
, Adresse Modbus
:
Baud Rate
,
Geschwindigkeit
: 19,2 kbps
Parity
,
Parität
:
Even
,
Gleich