MEASURED LIMITING VOLTAGE PERFORMANCE AND ELECTRICAL SPECIFICATIONS
Voltage
Code*
Circuit Type
Peak Surge
Current (Amps)
Per Mode
&
Per Phase
MCOV
ANSI/IEEE C62.41.1
TM
-2002, C62.41.2
TM
-2002, C62.45
TM
-2002, and C62.62
TM
-2010
Measured Limiting Voltages (tested with 6 inches of lead length external to the
enclosure per Clauses 6.1.1 of C62.62
TM
-2010 and 37.4.4 of ANSI/UL 1449-2006)
Test
Mode
Cat A,
30 Ω 100 kHz Ring Wave
2 kV / 67 A @ 270° Phase Angle
Category C (High) 10 kA
8/20 Current Driven Test
†
1P1
120 V, Single Ø
(2 wire + ground)
200,000 Per Mode
(L-N, L-G, N-G)
400,000 Per Phase
150
150
150
L-N
L-G
N-G
52 V
78 V
67 V
729 V
781 V
991 V
1S1
120/240 V, Split Ø
(3 wire + ground)
200,000 Per Mode
(L-L, L-N,
L-G, N-G)
400,000 Per Phase
320
150
150
150
L-L
L-N
L-G
N-G
56 V
52 V
78 V
67 V
964 V
729 V
781 V
991 V
3Y1
120/208 V, 3ØY
(4 wire + ground)
200,000 Per Mode
(L-L, L-N,
L-G, N-G)
400,000 Per Phase
320
150
150
150
L-L
L-N
L-G
N-G
56 V
52 V
78 V
67 V
964 V
729 V
781 V
991 V
3D1
120/240 V, 3Ø
(4 wire + ground)
200,000 Per Mode
(L-L, L-N,
HiLeg-N, L-G
HiLeg-G, N-G)
400,000 Per Phase
320
150
320
150
320
150
L-L
L-N
HL-N
L-G
HiLeg-G
N-G
56 V
52 V
40 V
78 V
66 V
67 V
964 V
729 V
1,374 V
781 V
1,414 V
991 V
3Y2
277/480 V, 3ØY
(4 wire + ground)
200,000 Per Mode
(L-L, L-N,
L-G, N-G)
400,000 Per Phase
550
320
320
320
L-L
L-N
L-G
N-G
40 V
40 V
66 V
53 V
1,758 V
1,374 V
1,414 V
1,661 V
3N2
240 V, 3
(3 wire + ground)
200,000 Per Mode
(L-L, L-G)
400,000 Per Phase
320
320
L-L
L-G
38 V
1038 V
964 V
1414 V
3N4
480 V, 3
(3 wire + ground)
200,000 Per Mode
(L-L, L-G)
400,000 Per Phase
550
550
L-L
L-G
104 V
1,559 V
1,758 V
2,071 V
Measured Limiting Voltage (MLV) Test Parameters:
Positive polarity, Category A: Line power applied, Category C: No line power applied, Voltages are peak (±10%). Measured Limiting Voltages are
measured from the insertion point on the sine wave to the peak of the surge for powered tests. Each phase is the average of the modes within that mode of protection. In order to duplicate the results, the
specified mode of protection must be tested in all modes (except N-G) and averaged together.
(
Individual mode or shot results may vary by more than 10%.
Scope Settings: Time Base = 10 microseconds
per division, Sampling Rate = 2.5 Gigasamples/sec, Bandwidth = 400 MHz (200 MHz for Cat C), Probes: Tektronix P5100/P6015A. These settings help to assure MLV results are accurate).
All tests
performed with 6” lead length (external to the enclosure), simulating actual installed performance.
The MLVs reported above are certified by Third-Party, Independent Testing. Individual test
reports are available upon request.
†
The MLV reported for the Category C High, 10 kA 8/20 Current Driven Test is determined by measuring the MLV of one of the fifteen 10 kA impulses impressed through the SPD during the Nominal
Discharge Current (In) Test from C62.62TM-2010 and ANSI/UL 1449-4
th
Edition. This is not the MLV recorded during the pre- and/or post-test 6 kV / 3 kA Combination Wave Test used to determine the
VPR of the SPD. The VPRs are reported on page 1 of this specification.
*Other voltage configurations may be available. Contact your sales representative for additional assistance.
Enclosure Dimensions
Inches
(mm)
Standard
Model
Enclosure Options
W
X
A
14.00
(356)
14.00
(356)
18.00
(458)
B
12.00
(305)
12.00
(305)
16.00
(407)
C
6.00
(153)
6.00
(153)
10.00
(254)
D
15.50
(394)
15.50
(394)
19.50
(496)
E
15.98
(406)
15.98
(406)
19.98
(508)
F
13.23
(309)
13.23
(309)
17.23
(411)
G
14.75
(375)
14.75
(375)
18.94
(482)
H
10.00
(254)
10.00
(254)
14.00
(356)
Type
NEMA
12
Steel
NEMA
4
Steel
NEMA
4X
Composite
lbs.
(kg)
30
(13.61
30
(13.61)
55
(24.95)
Model Number Example: CSMA403Y2D5
Base Model:
SPD Type and Nominal Discharge Current (I
n
) Rating:
kA
Voltage Code:
Options:
CSM
A = Type 2 SPD, I
n
= 10 kA
B = Type 2 SPD, I
n
= 20 kA
400
See Voltage Codes
3Y2
See Option codes
D5
Integral
Disconnect
D5, D6 option
configuration
(Enclosure
24x20x10)
(CSA)
SPD
Inside
Options
Description
AC10
Basic Internal Audible Alarm
AC11
Basic Internal Audible Alarm w/
on, off, and test
AC10S6
Basic Alarm/ Surge Counter
AC11S6
Basic Alarm w/ surge counter
on, off, and test
D5
(CSA)
Integral Disconnect Switch **
D6
(CSA)
Integral Disconnect Switch (no
external handle) **
E1
Hub on right side of enclosure
N
Removes N-G Tracking Circuit
P
Flush Mount Plate
R2
Remote LED's in separate
enclosure
S
Internal Surge Counter
W
NEMA 4 Metal Enclosure
X
NEMA 4X (Box-in-box) with
terminals
XS
NEMA 4X Stainless Steel
Corrosion Resistant Enclosure
Additional options may be available upon
request.
** Housed in a NEMA 4X Composite Enclosure