17
Heat Recovery Unit ILOX 129 - Installation, Operation and Maintenance
FläktGroup DC_10201GB_20190207_R2
We reserve the right to make changes without prior notice
INSTALLING A WATER HEATER
Connecting a water heater
INSTALLING A WATER HEATER
Connect the water coil to the heating system in the home; in parallel
with the radiators for example. Generally, thanks to the unit’s high effi-
ciency, no more heat output is needed than connecting the water coil to
the same branch as the underfloor heating for example.
The inlet is connected to the pipe using a thermostat valve, see the
adjacent figure.
Create an inspection opening if the connections are in a space above
a suspended ceiling. Install a bleed valve at the highest point of the
return line.
When the circuit has been topped up and bled, ensure that the water is
circulating in the coil before commissioning.
The system may need to be bled again after a few days. Ensure that
the air flows are calibrated before the water is connected. There must
be a continuous flow of water in the coil in winter due to the risk of
frost.
Return line Ø15 mm
Inlet line Ø15 mm
Thermostat valve
Shut-off valve
Pipes are not included in
the delivery from FläkGroup