V 1.9-EN

GIGATESTpro

USER’S

MANUAL

Summary of Contents for GIGATESTpro

Page 1: ...V 1 9 EN GIGATESTpro USER S MANUAL...

Page 2: ...instrument on and off standby auto power off 7 3 2 Notes and principles applicable to all measurements 7 3 3 Measurements of the particular functions 8 3 3 1 Voltage 9 3 3 2 Insulation resistance 10...

Page 3: ...ment cables connectors plugs or accessories exhibits visible damages The instrument was stored under unfavourable conditions for a long period The instrument was exposed to extraordinary stress caused...

Page 4: ...otected storage system of the test tips in the transport position sharp tips are safely hidden High contrast bright multicolour graphic OLED display ensures excellent legibility When measured under lo...

Page 5: ...e measuring tips are safely hidden Against accidental ejection are both parts secured by non contact magnetic latch Use original accessories only Max allowed voltage between test tip and ground is 300...

Page 6: ...ent on and off too RISO USPD key switches the measurement of insulation resistance and SPDs FUNC key has no function in RISO in USPD it enables to select another functions UTEST key to set test voltag...

Page 7: ...t of 4 NiMH AAA accumulators P 2011 test lead black 2 m P 3011 test tip black P 4011 crocodile clip black Note optional accessories P 2011 P 3011 respectively P 2011 P 4011 can be connected instead of...

Page 8: ...tched on again after about 1s 3 2 Notes and principles applicable to all measurements Select required parameter or function by the RISO USPD FUNC UTEST and UTEST keys The START key starts measurement...

Page 9: ...ect is deenergized before measurement Do not touch tested object or conductive parts of the test tips during measurement or after measurement until tested object is discharged RISK OF ELECTRIC SHOCK T...

Page 10: ...is displayed in the UIN area For AC voltage symbol is displayed For DC voltage symbol is displayed if the test tip on instrument s case is connected to or is displayed in case of the opposite polarity...

Page 11: ...inal test voltage is displayed in the UTEST area To set a different nominal test voltage hold down the key UTEST or UTEST until the voltage starts to rapidly increase or decrease Step is 1 V The exact...

Page 12: ...ars Tested object is automatically discharged by the instrument and it may take at large capacity up to tens of seconds Fig 3 7a Example of RISO measurement result discharging in progress Fig 3 7b Exa...

Page 13: ...you can select the desired type of SPD If the description of SPD includes symbol it means that it is a type in which care must be taken to the instructions of the manufacturer of SPD It may be e g th...

Page 14: ...The increase of the test current is displayed in bar graph The value of the test voltage is displayed in the UIN area The measuring cycle is completed automatically Read the measured insulation resist...

Page 15: ...ess the appropriate key to select the appropriate language Fig 3 11 Example of language selection menu After selecting the language the instrument enters the normal operating mode Illumination of meas...

Page 16: ...CD NiMH accumulators The batteries accumulators are continuously monitored see description in the Chapter 3 2 If batteries accumulators are low it must be replaced charged 4 1 1 Inserting and replacin...

Page 17: ...harge cycle is automatically executed see instruction manual for the charger used After the procedure the capacity of the accumulators should return to normal The above described cycle in stand alone...

Page 18: ...carbons etc 4 3 Calibration Measuring instruments should be regularly calibrated We recommend interval of calibration 1 year Furthermore we recommend carrying out calibration after each repair Contact...

Page 19: ...ge 250 1000 V Rmax 9 999 G Nominal test voltage Un 50 V 1000 V step 1 V Open circuit voltage 0 10 of the Un Nominal test current 1 mA Utest Un Short circuit current 3 mA Automatic discharge of tested...

Page 20: ...ovable test tip about 0 36 kg Reference conditions ambient temperature 23 2 C relative humidity 40 60 noncondensing instrument s position arbitrary Operating conditions ambient temperature 0 40 C rela...