background image

Mounting & Installation

Technical Data

Typical Schematic

Electrical & Mechanical

Control:  Via iLight network connection
iCANnet™ output current: 100mA Max @ nominal 15V
Rating:  32A* per channel @ 40ºC
Protection:  Provided by installer
Output channel current:  Maximum 12 x 32A*
(Total unit load not to exceed 192A)
Note: Fully loaded channels should be spaced every other channel to prevent heat buildup
Relay outputs:  Volt free capable of switching inductive and resistive loads
Terminal Sizes: Loads - maximum cable size: 1 x 10mm

2

 per circuit

Ambient temperature:  2°C – 40°C
Relative humidity:  5% - 95% max, non-condensing
IP rating:  IP20

Installation:  Installation must be carried out by a suitably qualified electrician and installed 

in a suitable DINrail enclosure.
Dimensions: 212mm (w) x 90mm (h) x 58mm (d)
Weight: 0.8kg

Software

For programming SCMR1232, Device Editor V2.11.1 is required 
(Packaged with iCANsoft V3.1.7 or later)

*  32A resistive per channel @ 40

0

C     -    20A capacitive per channel @ 40

0

C

SCMR1232

12 x 32A Relay Controller

Doc No: 9850-000782-03

SCMR1232 must be mounted in a suitable enclosure to provide regulatory 
protection from electric shock hazard as well as protecting the iCANnet 
data network from tampering that could lead to reduced network security. 

Ensure selected enclosure provides adequate cooling ventilation.

Fixing to DIN rail

1. Fix top clips over DIN rail. 
2. Pull down bottom clip using screwdriver.
3. Close module towards DIN rail.

4. Push up bottom clip to fix securely to DIN rail.

Removing from DIN rail

1. Pull down bottom clip with screwdriver.
2. Lift module away from DIN rail.

1

2

3

4

1

2

E&OE. iLight reserve the right to make 

changes to the equipment without 

prior notice. 

© Signify Holding

iLight

Usk House, Lakeside

Llantarnam Park,

Cwmbran, 

NP44 3HD, UK

t: +44 (0)1923 495495

e: [email protected]

www.iLight.co.uk

EU Authorised Representative

Cooper Lighting Netherlands B.V.

High Tech Campus

HTC 48

Eindhoven

5656 AE

Installation Guide

Dimensions

90mm

212mm

SCMR1232

Control Plate  Network Sensor

Control Plate 

iCANnet

Reviews: