IKI Wood burning stoves | Instructions for installation and use
IKI Wood burning stoves | Finnish high-quality craftsmanship
3.
Safety distances to flammable structures
Please note that the gap between the furnace and the stone mesh
must be loaded carefully with stones.
•
A.
From the stone mesh full of stones to the side
4 inches / 100 mm
•
B.
From the neck of the furnace to the side
10 inches / 250 mm
•
From the glass hatch to the front 31.5 inches / 800 mm
(Tip! Leave 39.5 inches / 1000 mm to have service space)
•
C.
From the chimney pipe loaded with stones and
equipped with a mesh to the side 10 inches / 250 mm
•
From the chimney pipe loaded with stones and equipped
with a mesh upward 20 inches / 500 mm
•
D.
From a chimney pipe without stones to the side
20 inches / 500 mm
•
From a chimney pipe without stones upward
39.5 inches / 1000 mm
3.1
Reducing the safety distances
•
50 % when using simple protection (i.e. 1mm metal/fiber board and a 30mm cavity)
•
75 % when using double protection (double protection board and a cavity)
ATTN!
The IKI ”Plus” version of the chimney pipe and upper mesh loaded with stones reduces the safety
distances 50 % compared to plain chimney pipe without stones.