IHP Shiloh36RWS Operation Instructions Manual Download Page 10

Comfortflame.US.com

900573-00N/C

10

14 

3

/

8

"

(36.5 cm)

30"

(76.2 cm)

1"

(2.5
cm)

1"

(2.5
cm)

Minimum Measurements

1"

(2.5 cm)

Opening "A"

Pitch

Slope

Opening "A" 

Max. 

Used Flashing

Model No. 

Flat

15"

V6F-8DM

0-6/12

26.6°

16 

1

/

8

"

V6F-8DM

6/12-

12/12

45.0°

20 

3

/

8

"

V12F-8DM

Figure 12 - Roof Opening Measurements

Nail Only 

Outer 

Perimeter 

of Flashing

Storm Collar

Flashing

Cone

Underlap Shingles 

at Bottom

Overlap 

Shingles Top 

and Sides Only

Figure 13 - Flashing Installation

Figure 14 - Storm Collar

Chimney 

Pipe

Waterproof 

Caulk

Storm 

Collar

Flashing

VENTING INSTALLATION

  

Continued

PENETRATING ROOF

To maintain a 1" clearance to the pipe on a roof with a pitch, a rect-

angular opening must be cut.
1.  Determine center point through which pipe will penetrate roof.
2.  Determine center point of roof. Pitch is the distance the roof drops 

over a given span, usually 12". A 6/12 pitch means that the roof 

drops 6" for each 12" one measure horizontally down from the 

roof rafters.

3.  Use roof opening chart (Figure 12) to determine the correct open

-

ing length and flashing required.

4.  Remove  the  shingles  around  opening  measured.  Cut  out  this 

section.

5.  Add next sections of pipe until end penetrates roof line. Check to 

see that the proper clearances are maintained. Extend chimney by 

adding sections of double wall pipe until pipe is minimum of 30" 

above the highest point of the roof cutout. Termination and chimney 

must extend a minimum of 36" above the highest point where it 

passes through the roof.

FLASHING INSTALLATION (V6F-8DM OR V12F-8DM)

Determine the flashing to be used with the roof opening chart. Slide 

flashing over pipe until base is flat against roof. Replace as many 

shingles as needed to cover exposed area and flashing base. Secure 

in position by nailing through shingles (see Figure 13). DO NOT NAIL 

THROUGH FLASHING CONE.

Installing Flashing on a Metal Roof

When installing flashing on a metal roof, it is required that putty tape be 

used between the flashing and roof. The flashing must be secured to the 

roof using #8 x 3/4" screws and then sealed with roof coating to prevent 

leakage through screw holes. A roof coating must also be applied around 

perimeter of flashing to provide a proper seal.

Storm Collar Installation (SC1 or SC2)

Place storm collar over pipe and slide down until it is snug against the open 

edge of the flashing (see Figure 14). Use SC1 for all round terminations 

and SC2 for all terminations with slip sections. Apply waterproof caulk 

around the perimeter of the collar to provide a proper seal.

Terminations/Spark Arrestor

The fireplace system must be terminated with the listed round top or 

chase terminations. In any case, refer to the installation instructions 

supplied with the termination. The termination approved for this fire-

place are the RT-8DM and RLT-8DM that can be used for flashing or 

chase and ET-8DM, ETO-8DM, ETL-8DM and ETLO-8DM for chase style 

termination only. Figure 15 shows an RLT-8DM round top termination.

 CAUTION: Do not seal openings on the rooftop 

flashing. Follow the installation instructions provided 

with the termination being used.

Terminations with 16" slip pipe sections are available. The RTT-8DM 

and RLTT-8DM are approved for flashing installations. When needed, 

these adjustable terminations may be used in combination with the 

pipe assembly to achieve the correct chimney height.

Note:

 In the rare instance there is a problem with the side driven rain 

or wind or the chimney is not drafting properly, an ADS-8DM (Anti-

Draft Shield) can be used with round terminations.

Summary of Contents for Shiloh36RWS

Page 1: ...re installation to determine the need to obtain a permit POUR LE CANADA L autorité compétente comme le service municipal du bâtiment les pompiers etc doit être contacté avant l installation afin de déterminer la nécessité d obtenir un permis This appliance may be installed in an aftermarket permanently located manufactured home USA only or mobile home where not prohibited by local codes This appli...

Page 2: ...n and Maintenance Guidelines 13 Replacement Parts 15 Technical Service 15 Parts 16 Accessories 18 Warranty 23 Thank you for your purchase We appreciate your business Please carefully read and follow all instructions in this manual Pay special attention to all warnings and safety information Following these safety care and operation instructions will help ensure many years of dependable and enjoyab...

Page 3: ...sed to treat insects and fungus When burned thesechemicalscanposeasignificanthazard WARNING BURNING IMPROPER FUEL I E CHARCOAL CAN RESULT IN CARBON MONOXIDE POISONING WHICH MAY LEAD TO DEATH Carbon Monoxide Poisoning Early signs of carbon monoxidepoisoningresemblethefluwithheadaches dizziness or nausea If you have these signs get fresh air at once Have the appliance inspected by a qualified servic...

Page 4: ...LE WALL BOARD 0 TO TOP SPACERS NO COMBUSTIBLE MATERIAL ON FACE GAS LINE KNOCK OUTS AIR KIT KNOCK OUT GAS LINE KNOCK OUTS ELECTRICAL OUTLET LEFT SIDE RIGHT SIDE 37 41 35 21 8 22 1 41 1 29 20 1 2 9 1 8 9 1 8 7 1 8 3 1 2 3 1 2 8 3 4 8 3 4 11 1 4 14 1 4 41 1 4 32 1 2 11 3 4 5 8 11 1 2 14 1 2 SQUARE CHASE TOP TERMINATION ROUND TOP TERMINATION CAUTION THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME FL...

Page 5: ...ts air conditioning ducts windows or doors 3 A location that avoids the cutting of joists or roof rafters will make installation easier 4 An outside air kit is available with this fireplace seeOptional Outside Air Kit on page 6 MINIMUM CLEARANCE TO COMBUSTIBLES Ceiling 40 minimum Back and sides of fireplace 3 4 minimum Floor 0 minimum Perpendicular wall to opening 12 minimum Top spacers 0 minimum ...

Page 6: ...late brick concrete metal glass marble stone etc Provide a means to prevent hearth extension from shifting and seal gap between fireplace frame and hearth extension with a non combustible material such as sand cement grout see Figure 3 WARNING Hearth extension is to be installed only as shown in Figure 3 Figure 3 Hearth Extension Seal Gap Fireplace Front Ember Protector Fireplace Front Raised Hear...

Page 7: ... then be installed over the flue pipe section with the hemmed end up Press down on each pipe section until the lances securely engage the hem on the fireplace starter The wire will as sure the proper spacing between the inner and outer pipe sections Continue to assemble chimney sections as outlined making sure that both the inner and outer pipe sections are locked together When installing double w...

Page 8: ... Detail B Ceiling Support Pipe 12S 8DM USING ELBOW OFFSETS 30E 8DM 1 To achieve desired offset you may install combinations of 12 18 24 36 and 48 length of double wall pipe see offset chart and Figure 7 2 Chimney weight above offset rests on return elbow Straps must be securely nailed to rafters or joists see Figure 8 details A and B 3 Maximum length of pipe between supports return elbow or 12S 8D...

Page 9: ...rews or Staples Min of 8 Existing Ceiling Frame VENTING INSTALLATION Continued FIRESTOP SPACERS 3600FS 8DM 1 Firestopspacersarerequiredateachpointwherethechimneypenetrates a floor space Their purpose is to establish and maintain the required clearance between the chimney and the combustible materials When the pipe passes through a framed opening into a living space above the firestopmustbeplacedon...

Page 10: ...s many shingles as needed to cover exposed area and flashing base Secure in position by nailing through shingles see Figure 13 DO NOT NAIL THROUGH FLASHING CONE Installing Flashing on a Metal Roof When installing flashing on a metal roof it is required that putty tape be used between the flashing and roof The flashing must be secured to the roof using 8 x 3 4 screws and then sealed with roof coati...

Page 11: ...sses through the roof and must be at least 2 feet above the highest point of the roof that is within a horizontal distance of 10 feet see Figure 17 FINISHING FIREPLACE Combustiblematerials suchaswallboard sheetrock drywall plywood etc may make direct contact with sides and top around the fireplace face It is important that combustible materials do not overlap the face itself Brick glass tile or ot...

Page 12: ...connections must be tested for leaks after the installation is completed After ensuring that the gas valve is on apply soap and water solution to all connections and joints Bubbles formingshowaleak Correctallleaksatonce DONOT USEANOPENFLAMEFORLEAKTESTINGANDDONOT OPERATE ANY APPLIANCE IF A LEAK IS DETECTED LEAK TESTING SHOULD BE DONE BY A QUALIFIED SERVICE PERSON Note An IHP hood must be installed ...

Page 13: ...e use of the appliance imme diately if doors are damaged and contact a qualified installer for repair Only doors certified with the ap pliance shall be used WARNING Do not slam or strike doors Damage can result in a hazardous condition Cleaning Glass Clean the glass with any commercial glass cleaner or soap and water Do not use any abrasive material to clean the glass Do not clean the glass with a...

Page 14: ...rth refractory may have shifted or moved out of place while fireplace was in transit These coverplatesmustbekeptintheproperlocationpriortousingthefireplace See Figure 23 For further operating guidelines instructions and warranty infor mation please refer to your homeowner s guide or contact your authorized dealer Figure 23 Locating Access Cover Plate Access Panel ...

Page 15: ...plied from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model number of the fireplace 2 The serial number of the fireplace 3 The part number 4 The description of the part 5 The quantity required 6 The installation date of...

Page 16: ...Comfortflame US com 900573 00N C 16 PARTS 9 24 16 31 25 16 4 30 32 19 12 23 20 28 17 8 1 5 21 2 18 11 14 3 13 22 10 6 29 7 33 34 26 27 15 MODEL NO CATALOG NO Shiloh36RWS F2554 ...

Page 17: ...ory Brick Liner 1 12 J4472 Bottom Rear Refractory Natural White Brick Liner 1 13 J4474 Bottom Front Refractory Natural White Brick Liner 1 14 J3972 Firebox Support Leg 4 15 Damper Can Collar 1 16 J8012 Kit Screen Assembly 1 17 Firebox Top Assembly 1 18 J3980 Air Kit Door Assembly 1 19 Face Weldment 1 20 J4470 Air Deflector 1 21 Fireplace Top Insulation 1 22 J4052 Access Panel 1 23 J4491 Grate 1 24...

Page 18: ...Hi Temp Double Wall Pipe Snap Lock F0882 18 8HT 18 Section Hi Temp Double Wall Pipe Snap Lock F0883 24 8HT 24 Section Hi Temp Double Wall Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp Double Wall Pipe Snap Lock 30 OFFSET AND RETURN F0900 30E 8DM 30 Degree Offset and Return OPTIONAL OUTSIDE AIR KIT FOR FLOOR INSTALLATION F1091 AK4 Complete...

Page 19: ...F0921 ETL 8DM Square Top with Slip Section F0893 ETL 8HT Hi Temp Large Pyramid Top with Slip Section MESH SQUARE TOP TERMINATION F0922 ETO 8DM Square Top with Mesh MESH SQUARE TOP TERMINATION WITH SLIP SECTION F0923 ETLO 8DM Square Top with Mesh and Slip Section STAINLESS STEEL HOOD Required when installing a vent free gas log in this fireplace F1052 HS36 36 Stainless Steel Hood w 4 Brow DRAIN PAN...

Page 20: ... Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp Double Wall Pipe Snap Lock F0886 30E 8HT 30 Degree Hi Temp Offset and Return F0887 12S 8HT Hi Temp Chimney Support For Use With Chimney Heights In Excess of 30 F0888 RT 8HT Hi Temp Round Top with Mesh Screen F0889 RTT 8HT Hi Temp Round Top with Mesh Screen and Slip Sec tion F0890 RLT 8HT Hi T...

Page 21: ...________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____________________________________...

Page 22: ...________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____________________________________...

Page 23: ...atural or propane gas Fuel products with abnormal burning characteristics including but not limited to fuel such as driftwood coal or plywood and wood products using a binder may burn at excessive temperatures and may cause damage to the Product or may cause it to function improperly c damages caused by failing to provide proper maintenance and service in accordance with the instructions provided ...

Page 24: ...ecolors stylesandproducts Consult your local distributor for fireplace code information Printed in U S A 2015 IHP LLC P N 900573 00 Rev N C 10 2015 P900573 00 WARRANTY KEEP THIS WARRANTY 1508 Elm Hill Pike Suite 108 Nashville TN 37210 Model Number Serial Number Date Installed Dealer s Name Dealer s Phone Number Keep receipt for warranty verification ...

Reviews: