IHP AK4 Quick Start Manual Download Page 1

AK4 OUTSIDE COMBUSTION AIR KIT

[FOR USE WITH APPLIANCE MODELS MISSION36/42, ALPHA32/36, MARQUEE36/42/50, TAURUSST/PF, VALIANT32, VEGA32/36/42, PLANTATION48, GEORGIAN36/42/50, INGLENOOK36, WINSDORST, MONTEREYPF, 
CRAFTSMANST, CRAFTSMAN36/42, BRT4536/42, BRT4336/42, BRT4536/42, BRT4036/42, BRT2532/36, BRT2032, BRT2332, VRT4032/36, VCT4032/36, VCM3026, VRT6036/42/50, VRT4536/42/50, VRT43ST/PF, VRT3032/36/42, 
VCT3032/36/42, VRT2036/42, VCT2036/42, WRT6842/50, WRT6036/42/50, WRT4842/50, WRT4536/42/50, WRT40CR/CL, WCT40CR/CL, WRT40ST/PF, WRT35ST, WRT3836, WCT3836, WRT3036/42, WCT3036/42, WRT2036/42, 
WCT2036/42, BELMONT36/42/50, COLUMBUS36/42, BLACKSTONE36/42, BARKLEYST/PF, CUMBERLAND32/36/42, OAKRIDGE36/42]

AK4 OUTSIDE COMBUSTION AIR KIT

P/N 127169-01
Rev. B, 03/2017

HEARTH PRODUCTS

KITS AND ACCESSORIES

GENERAL INFORMATION

Combustion Air Kit model AK4 is designed to provide outside air to 
the fi re for combustion.

READ ALL THE STEPS BEFORE STARTING THE INSTALLATION

THE FIREPLACE MUST BE OFF AND COLD BEFORE BEGINNING.

ALL WARNINGS, PRECAUTIONS AND INSTRUCTIONS IN THE 
INSTALLATION AND OPERATION MANUAL PROVIDED WITH THE 
APPLIANCE APPLY TO THESE INSTRUCTIONS.

If you encounter any problems, need clarifi cation of these instructions
or are not qualifi ed to properly install this kit, contact you local 
distributor or dealer.

If any of these parts are missing or damaged, contact your dealer or 
IHP.us.com for referral information.

KIT CONTENTS

1 ea. Collar
1 ea. Hood
1 ea. Flex Duct, 4" x 3'
1 ea. Instruction Sheet

Cat. No.

Model

Description

F1091

AK4

Complete 4" Air Kit with Collar, Hood and 3' Flex

1

INSTALLATION INSTRUCTIONS

1.  Locate air inlet cover plate on fi replace's outer surround and remove 

it. Cut-out any visible insulation that may obstruct air fl ow. Air inlet 
tube may be installed in two positions

 (

Figure 2

(AK4E only). In-

sert inner tab of inlet tube into the mating slot next to the opening 

(

Figure 1

)

. Place outer tab of inlet tube over mating hole next to the 

opening and secure with a screw previously removed from cover 
plate. Seal any remaining gaps around inlet tube with hi-temp duct 
tape or noncombustible sealant 

(

Figure 3 or 4

).

2.  Construct a 4 1/2" x 4 1/2" framing or opening on exterior wall (see 

Figure 3 or 4). Install the outside air vent termination in a location 
that would not eventually be obstructed by bushes, snow, or other 
obstructions.

 

Also, locate the vent near the fi replace to make fl ex duct instal-
lation easier. The fl ex duct supplied measures approximately 10" 
compressed and up to approximately 3 feet extended

 (

Figures 3 or 

4

).

 

Be very careful not to distort fl ex duct when extending and watch for 
sharpness at the edges (use gloves). Slip fl ex duct onto inlet collar 
and vent collar. Clean fl ex duct surface of oil and dirt at the ends 
and secure fl ex duct to collars with hi-temp duct tape to provide a 
good seal.

Cut Out Any
Visible
Insulation

Insert Inner Tab of 
Inlet Tube into Slot
on Outer Surround

Figure 1

  

CAUTION

AIR INLET DUCTS ARE NOT TO TERMINATE IN ATTIC 
SPACE.

DO NOT INSTALL VENT TERMINATION IN A LOCATION 
THAT WOULD DRAW AIR FROM GARAGE OR ATTIC 
SPACES.

NOTICE

The maximum height for the air vent can not exceed 
3 feet below the fl ue gas outlet of the termination.

IHP.us.com