IGM Vega FD 330-4-1 User Manual Download Page 23

MRBP.425241.001-01 UM version 1.1 01.05.2022   FD 330-4-

1 «Vega»

 

23 

 

 

9.2  Factory default 

Table 2 

№  Operation 

mode 

Description 

Factory 
default 

Notice 

1. 

«Far – 
near

» 

Far 25 meters 
Near 15 meters 

Far 

Switching using the service 
program 

2. 

«Fast-slow»  Fast – standard mode 

Slow 

– analysis of simultaneous 

operation of UV and IR 
channels, delay for issuing a fire 
signal 5 sec 

Slow 

In the slow mode, high noise 
immunity, response time is not 
more than 30 seconds. 
Switching using the service 
program 

3.  Fire fixation 

Fixing the fire mode  

w/o fixation 

Removing the fire mode using 
the service program, removing 
the power supply and a 
magnetic key. Switching using 
the service program 

5.  Failure 

fixation 

Fixing the failure mode, due to 
the dustiness of the input 
windows, an increased level of 
IR or UV interference, according 
to the results of self-testing. 

with fixation 

Removing the mode by turning 
off the power or using the 
service program (sequentially 
turning off and then turning on 
the fixation mode) 
Switching using the service 
program 

6.  Heating  

Heating of the optical part of the 
detector to prevent 
condensation and icing.  

Turned off 
Heating turn-
on point +30 

Switching using the service 
program. 
To calculate cable products, 
refer to the appendix for 
information on power 
consumption with heating on 

Relays 

«Fire» and «Failure» have NC and NO contact groups. The company produces 

detectors with the following relay configuration: 

«Fire» relay – normally open (always open when power off, closed when power on and 

fire detected) 

«Failure»  relay  –  normally  open  (always  open  when  power  off,  closed  when  power  on 

and instrument availability) 

On  request,  manufacturing  of  the  detectors  with  normally  closed  contact  relay 

groups is possible. 

«Fire» relay – normally closed (always closed when power off, open when power 

on and fire detected) 

«Failure»  relay  –  normally  closed  (always  closed  when  power  off,  open  when 

power on and instrument availability) 

 

Summary of Contents for Vega FD 330-4-1

Page 1: ...dress 27 Engels Prospect building 5 litera A Saint Petersburg 194156 Russia Tel 8 800 234 66 90 Website www igm pribor com E mail support igm pribor ru 1 Flame detector FD 330 4 1 Vega User manual MRB...

Page 2: ...able gland 12 8 Detector connection 13 8 1 Power source requirements 13 8 2 Detector connection 13 Connecting a detector to digital channel RS 485 13 5 1 Connection diagrams 14 9 Commissioning 18 Outp...

Page 3: ...ixture of vapors of petroleum products natural gas and other hydrocarbons explosive and fire hazardous facilities of the oil and gas as well as fuel and energy complexes including production sites tra...

Page 4: ...p to 95 short term exposure to 100 humidity is allowed Supply voltage Nominal 24 VDC Range 18 32 VDC FD 330 4 1 VEGA power consumption Stand by mode not more than 2 VA Alarm mode not more than 3 VA Wi...

Page 5: ...g to GOST 30546 1 98 the impact of earthquakes with an intensity of 9 points according to MSK 64 at an installation level above the zero mark up to 10 m Immunity to direct mechanical impact with an en...

Page 6: ...ability check in conditions of standard mounting without disconnection from the external actuating alarm system Sunshield protects the optical elements of the sensors from the adverse effects of the e...

Page 7: ...MRBP 425241 001 01 UM version 1 1 01 05 2022 FD 330 4 1 Vega 7 5 Configuration and operation 5 1 Appearance Figure 1 FD 330 4 1 VEGA appearance...

Page 8: ...ntroller according to a given algorithm to increase the reliability of the alarm output The program highlights the useful signal from the background As a result of signal processing a decision is made...

Page 9: ...30 4 1 VEGA in places where combined disturbance may occur welding radio station 5 W 100 MHz welding device vibration with an acceleration 10 g It is not recommended to use radio station in a distance...

Page 10: ...s 3 05 05 84 Technological equipment and process pipelines Detectors mounting must be carried out with the power supply switched off Detector repair is allowed only to the personnel of the manufacture...

Page 11: ...ce of a possible fire Figure 1 Wrong orientation of the detector Correct orientation of the detector Figure 3 Installation relative to the horizon It is necessary to visually estimate the area viewing...

Page 12: ...ressive environment in places exposed to stray currents 7 While FD 330 4 1 VEGA mounting it is necessary to check the condition of the ex proof parts subjected to disassembly for compliance with the r...

Page 13: ...ignal using and digital output using mode Figures 8 and 9 show diagrams of connecting two detectors to fire alarm control system via RS 485 interface with and w o terminal box install the FD 330 4 1 V...

Page 14: ...ine beyond 1200 m must be carried out by inserting an interface repeater into the line 5 It is advisable to power the FD 330 4 1 VEGA according to the beam scheme each tank has its own cable Allowable...

Page 15: ...25241 001 01 UM version 1 1 01 05 2022 FD 330 4 1 Vega 15 Figure 5 Connection diagram for an ultra explosion proof detector EEx de Figure 6 Connection diagram for a detector with uninsulated output 4...

Page 16: ...01 UM version 1 1 01 05 2022 FD 330 4 1 Vega 16 Figure 7 Connection diagram for an explosion proof detector via RS 485 interface Figure 8 Connection diagram for two explosion proof detectors EEx via R...

Page 17: ...MRBP 425241 001 01 UM version 1 1 01 05 2022 FD 330 4 1 Vega 17 Terminal box Figure 9 Connection diagram for two detectors and a digital channel RS 485 via terminal box...

Page 18: ...4 1 VEGA using 4 20mA and HART Notice 250 Ohm is necessary to ensure the correct operation of the HART interface in case of 4 20 mA controller low resistance it is not necessary to install resistance...

Page 19: ...for FD 330 4 1 VEGA different states Table 1 FD 330 4 1 VEGA state Fire relay contacts state Failure relay contacts state Output signal mA LED indicators state 1 No supply voltage Open Open 0 Off 2 Af...

Page 20: ...01 05 2022 FD 330 4 1 Vega 20 It is possible to change the sensitivity and signal processing time to reduce the effect of interference when identifying a fire or a nearby location of the alleged fire...

Page 21: ...heck the detector s functionality by the method of illumination by a test radiation source it is necessary to do the following 1 Direct the test source to the flame detector located at a distance of u...

Page 22: ...digital output signals At the same time FD 330 4 1 VEGA continues analyzing incoming optical signals For visual status indication a three color LED indicator is installed on the front of the detector...

Page 23: ...ing the mode by turning off the power or using the service program sequentially turning off and then turning on the fixation mode Switching using the service program 6 Heating Heating of the optical p...

Page 24: ...uld be sent for repair to the manufacturer The grounding condition is checked by the wiring complexity and the presence of grease on the contacts Functionality check procedure is described in the Manu...

Page 25: ...or storage conditions 1 in accordance with GOST 15150 69 The method of packaging preparation for packaging shipping containers and materials used in packaging the order of placement correspond to the...

Page 26: ...meeting storage conditions of this UM In the event of a warranty claim please contact the manufacturer Address 27 Engels Prospect Building 5 Saint Petersburg 194156 Russia Tel 8 800 234 66 90 Website...

Page 27: ...signed number lower byte determines the exchange rate over the RS 485 channel 0x01 1200 baud 0x02 2400 baud 0x04 4800 baud 0x08 9600 baud 0x10 19200 baud 0x02 16 bit register of the detector s state w...

Page 28: ...g the rate and or the detector s number the upper level controller receives a response to the command at the same speed and only after that FD 330 4 1 VEGA changes the exchange rate and detectors numb...

Page 29: ...MRBP 425241 001 01 UM version 1 1 01 05 2022 FD 330 4 1 Vega 29 Appendix B Ex protection drawing...

Page 30: ...M version 1 1 01 05 2022 FD 330 4 1 Vega 30 Revision history sheet Chang e Sheet number pages Total sheet number pages of the docum ent of the accom panyin g docum ent and date Signature Date change d...

Reviews: