5.2 Installation
Secure with protection class in accordance with current regulations
With top-hat DIN rail mounting for standard DIN46277 35 mm carrier rail
•
Snap the device on the standard carrier rail.
•
Loosen the fastening screws and remove the hood from the base.
•
Connect to power supply (see Section 5.3).
Without top-hat DIN rail mounting
•
Loosen the fastening screws and remove the hood from the base.
•
Loosen screws and remove the DIN rail adapter.
•
Drill the marked points in the base with a Ø4.3 mm drill.
•
Fit base on base plate with 2 M4 screws.
•
Connect to power supply (see Section 5.3).
5.3 Electrical connection
The device terminal strip is live during operation!!
Before working on the device disconnect it from the mains!!
The device must be protected mains-side by the operator with a max. 2A fuse!
If inductive consumers are connected, voltage peaks occur when switching
off. For this reason, connected inductive consumers (e.g. contactors) must be
provided additionally with an RC circuit: e.g. 0.1µF / 100Ω.
Caution electrical voltage
Caution
Caution electrical voltage
7