20
Probe malfunctions:
If the probe electronics report a malfunction, this will also be displayed.
Error
code
Description
Cause
Remedial Action
102
Fault in the probe
hardware
e.g. broken cable, hardware
fault
Replace probe
103
Calibration error
0% or 100% not calibrated or
wrong way round; calibrated
measuring range too small
Repeat calibration
105
Probe temperature too
high, occurs with
T
probe
≥105°C
Ambient temperature of probe
probably too high
Heat insulation measures on
the flange must
not
be
carried out
on the electronic
part
106
Connection problem
Fault
e.g. broken cable, connections
wrong way round
Check wiring
Every error code
(except “8.8.8”) causes the extra relay to be switched off.
The 4 mA .. 20 mA output then jumps to 0 mA within under 3 s
The flashing code „120“ is active if the level limit is passed. This is not
considered an error code. The 4 mA .. 20 mA output stays at its level
equivalent value.
120
fill level exceeded
fill level above limit
reduce liquid level