UK
15
Set time
DINT
4 bytes
Set time, always UTC, format:
- VSE150: U32: 0x00ssmmhh
- VSE151: U32: 0x00hhmmss
- VSE152: U32: 0x00hhmmss
- VSE153: U32: 0x00hhmmss
Set counter ID
Byte
1 byte
Set ID (1���32) of the counter
Set counter value
DINT
4 bytes
Set value of the counter selected with the
ID (in seconds)
8.3 Register
8.3.1 Modbus TCP device identification register
Address
Access Length
(word)
Request
Parameter
39000
R
30
vendor name
"ifm electronic"
39030
R
20
product name
"VSE153"
39050
R
2
production status of
the unit
"AA"
39052
R
10
firmware version
"V1�0�0"
39062
R
2
serial Number
defined in the product process
39064
R
20
short description
device
diagnostic electronics VSE153
8.4 Modbus TCP register mapping input (FC4)
Register no.
IEC61131 address Access
Memory area
30001…30512
%IW0…%IW511
r
input area
8.5 Modbus TCP input function code
function code
Parameter
Code 4 (dec)
read input register
8.6 Modbus TCP register mapping output (FC3, FC6 and FC16)
Register no.
IEC61131 address Access
Memory area
40001…40512
%QW0…%QW511 r/w
output area
Summary of Contents for VSE153