IFM UGR500 Operating Instructions Download Page 4

4

6  Settings

The unit and the parameters are set via the IO-Link interface (

→ 6.1) or the 

teach button (

→ 6.2).

6.1  IO-Link

This unit has an IO-Link communication interface which enables direct access to 

process and diagnostic data. In addition it is possible to set the parameters of the 

unit while it is in operation. Operation of the unit via an IO-Link interface requires 

an IO-Link master.
With a PC, suitable IO-Link software and an IO-Link adapter cable communication 

is possible when the system is not in operation.
The IODDs necessary for the configuration of the unit, detailed information about 

process data structure, diagnostic information, parameter addresses and the 

necessary information about the required IO-Link hardware and software can be 

found at www.ifm.com.

6.2  Teach button
6.2.1  Start programming mode.

 

Press the teach button for 2 s...6 s.

 

>

Yellow status LEDs 1/2 flash (1 Hz), the unit is in the programming mode.

If programming has not been completed successfully, the unit returns to the 

previous setting.

6.2.2  Adjust the unit to the reflector

The sensor is operational once the reflector has been aligned to it.

 

Start programming mode 

(→ 6.2.1)

.

 

► Align the reflector to the unit (fig. 1).

 

Press the teach button for 1 s.

 

>

Yellow status LEDs 1/2 flash (2.5 Hz), adjustment is completed.

6.2.3  Invert output response

 

Press the teach button for > 6 s.

 

>

Yellow status LEDs 1/2 flash (> 10 Hz).

 

Output function is inverted.